Fig. 3:
Adjust the rear 482.6 mm (19") mounting angle
If necessary, fit a partition.
The use of a partition is optional, depending on the application. It improves the
air circuit by separating the cold and warm air zones, which in turn prevents air
short circuits. Any unused height units should be sealed with blanking panels.
– Partitioning: Air baffle plates for TS IT 482.6 mm (19") mounting frame
5501.xxx
5
Installing the air duct
Attach the eight 482.6 mm (19") fasteners to the front and rear 482.6 mm (19")
mounting angles as shown in fig. 4.
Fig. 4:
Install the 482.6 mm (19") fasteners
Loosely screw four pan-head screws M5x16 (pan-head screw I14583/5X16/
TX25), each with one plastic washer (washer NZ/5.5), into the positions shown.
The screws must be screwed into the front and rear 482.6 mm (19") mounting
angles on the left and right side as shown in fig. 5 and fig. 6.
Note:
The screws should only be screwed in partially with a few turns of the
thread so that they are held securely in position.