Outdoor Fault Codes
Fault code
Fault description
17
Discharge temperature
sensor fault
18
AC voltage is abnormal
19
Suction temperature
sensor fault
22
The defrosting sensor fault
23
Expansion valve A tube
(thin) sensor fault
24
Expansion valve B (thin)
tube sensor fault
25
Expansion valve C (liquid)
pipe sensor fault
26
Expansion valve D (liquid)
pipe sensor fault
84
TROUBLESHOOTING
Possible reasons for
abnormality
"1.The wiring of the discharge
temperature sensor is
connected loosely;
2.The discharge temperature
sensor fails;
3.The sampling circuit is
abnormal."
1.The AC voltage>275V or
<160V.
2.The AC voltage of sampling
circuit on the driver board is
abnormal.
"1.The wiring of the suction
tempe‑ rature sensor is
connected loosely;
2.The suction temperature
sensor fails;
3.The sampling circuit is
abnormal."
"1. The wiring of the defrosting
sensor
is connected loosely;
2. The defrosting sensor fails;
3. The sampling circuit is
abnormal."
"1. The wiring of the sensor
for the expansion valve A(thin
tube) connect loose;
2. The sensor for the
expansion A(thin tube) is
failure;
3. The sampling circuit is
abnormally"
"1. The wiring of the sensor
for the expansion valve B (thin
tube) connect loose;
2.The sensor for the expansion
valve B(thin tube) is failure;
3.The sampling circuit is
abnormally"
"1. The wiring of the sensor for
the expansion valve C (liquid
pipe) is connected loosely;
2. The sensor of the expansion
valve C (liquid pipe) fails;
3. The sampling circuit fails."
"1.The wiring of the sensor for
the expansion valve D (liquid
pipe) is connected loosely;
2.The sensor of the expansion
valve D (liquid pipe) fails;
3.The sampling circuit fails."
How to deal with
"1. Reconnect the wiring of
the discharge temperature
sensor;
2. Replace the discharge
temperature sensor fails;
3. The sampling circuit is
abnormal."
"1. Normal protection,
please check the supply
power;
2. Replace the driver board."
"1. Reconnect the wiring
of the suction temperature
sensor;
2. Replace the suction
temperature sensor;
3. Replace the outdoor
control board."
"1. Reconnect the wiring of
the defrosting sensor;
2. Replace the defrosting
sensor;
3. Replace the outdoor
control board."
"1. Reconnect the wiring of
the sensor for the expansion
valve A (thin tube);
2. Replace the sensor for
the expansion valve A (thin
tube);
3. Replace the outdoor
control board."
"1. Reconnect the wiring of
the sensor for the expansion
valve B(thin tube);
2.Replace the sensor for
the expansion valve B(thin
tube);
3. Replace the outdoor
control board."
"1. Reconnect the wiring of
the sensor for the expansion
valve C (liquid pipe).
2. Replace the sensor for the
expansion valve C (liquid
pipe);
3. Replace the outdoor
control board."
"1. Reconnect the wiring of
the sensor for the expansion
valve D (liquid pipe);
2. Replace the sensor for the
expansion valve D (liquid
pipe);
3. Replace the outdoor
control board."