Product Specifications 18K, 24k and 36k Outdoor Condensor
Multi-Zone Flex
Model Name
Dimension & Weight
Net Dimension (WxHxD)
Net Weight
Package Dimension (WxHxD)
Gross Weight
Piping
Diameter(Liquid)
Diameter(Gas)
Min/Max Length (Each)
Max Length
(Total)
Max Height
Factory Refrigerant Charge
Additional Refrigerant Charge
Note: refer to table 433.1 in the
Installation section for details.
Installations using 24k indoor units
require addtional calculations.
1. Test conditions
Cooling : Indoor: DB80 °C/ WB 67ºF Outdoor: DB95 °C/ WB75°F
Heating: Indoor: DB70 °C/ WB 60ºF Outdoor: DB47 °C/ WB 43 °F
2. The Sound Pressure Level is based on the following conditions:
Outdoor unit:
Measure the noise value of 3 points, the points are 3'(ft) in front of the three sides of the unit surface.
(front/left/right)and height =1/2(unit height +3) ft from floor level, and calculate the weighted average of the noise.
3. The above data was measured in an anechoic chamber. Please take into consideration reflected sound of your specific
application environment.
4. All specifications are subjected to change by the manufacturer without prior notice.
15
SPECIFICATIONS
2 Indoor units
FPHMR18A3A
inch
39x17 3/4x28 3/4
lbs
108.0
inch
39x17 3/4x28 3/4
Ibs
119
inch
1/4
inch
3/8
ft
25/82
ft
164
ft
49
oz
63.49
oz/ft
(L-50 ft * 0.16 oz./ft)
2 or 3 indoor units
2 to 4 indoor units
FPHMR24A3A
FPHMR36A3A
43 3/8x18 1/8x36 1/4
43 3/8x18 1/8x47 1/4
158.73
188.5
43-3/8x18-1/8x36-1/4
43-3/8x18-1/8x47-1/4
169.76
220.5
1/4
1/4
3/8
3/8
25/66
25/66
197
246
49
49
81.13
105.82
(L-75 ft * 0.16 oz./ft)
(L-100 ft * 0.16 oz./ft)
2 to 5 indoor units
FPHMR42A3A
43 3/8x18 1/8x47 1/4
85.5
43 3/8x18 1/8x47 1/4
220.5
1/4
3/8
25/66
262
49
120
(L-125 ft * 0.16 oz./ft)