Uponor Combi Port M-XS Installation And Operation Manual
Uponor Combi Port M-XS Installation And Operation Manual

Uponor Combi Port M-XS Installation And Operation Manual

Hide thumbs Also See for Combi Port M-XS:

Advertisement

Quick Links

Uponor Combi Port M-XS
EN
Installation and operation manual
SD0000126

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Combi Port M-XS and is the answer not in the manual?

Questions and answers

Summary of Contents for Uponor Combi Port M-XS

  • Page 1 Uponor Combi Port M-XS Installation and operation manual SD0000126...
  • Page 2: Table Of Contents

    Zone valve and actuator ............12 Differential pressure regulator..........13 Maintenance................ 14 General information.............. 14 Turning off heat interface unit..........14 Setting log heat interface units..........15 Troubleshooting..............16 Fault description..............16 Uponor Combi Port M-XS Installation and operation manual...
  • Page 3: Copyright And Disclaimer

    Under no circumstances shall Uponor be liable for any indirect, For any questions or queries, please visit the local Uponor website or special, incidental or consequential damages or loss that result speak to your Uponor representative.
  • Page 4: Preface

    Risk of injury and damage. Ignoring warnings can cause components. personal injury and/or damage to products and other property. Uponor is not liable for damage caused by ignoring the instructions in this document or the applicable building code. Caution! Risk of malfunctions. Ignoring cautions can cause the 2.2 Standards and regulations...
  • Page 5 Business users should contact their supplier and check the terms and conditions of the purchase contract. Do not dispose this product with other commercial waste. Uponor Combi Port M-XS Installation and operation manual...
  • Page 6: System Description

    It can cool down which is beneficial for In the Combi Port M-XS unit, the cold water is heated only when the hygiene. required following the flow-through principle with a stainless steel high performance plate heat exchanger.
  • Page 7: Components

    HIU in different expansion stages. Note Thermostats and remote control modules are not part of the Combi Port delivery. They must be ordered separately. SD0000161 Uponor Combi Port M-XS Installation and operation manual...
  • Page 8: Prepare For Installation

    The limit values can be found in our technical information. The heating water quality must be in accordance to VDI 2035. In case of warranty claims, the report must be presented. Uponor Combi Port M-XS Installation and operation manual...
  • Page 9: Installation

    Install the pipes in accordance with the planning Connect the HIU electrically documentation. Connect optional room control if applicable 5.4 Filling and flushing Fill and flush the system according to local regulations and standards. Uponor Combi Port M-XS Installation and operation manual...
  • Page 10: Tightness Testing

    Incorrect finishing of the installation can lead to property damage. Follow these steps and finish the installation: Check the settings. Complete the acceptance/ finishing protocol. Hand over the documentation and the protocol to the homeowner. Uponor Combi Port M-XS Installation and operation manual...
  • Page 11: Operation

    6.4 Circulation pump Note See the documentation from the circulation pump CD0000430 supplier as well as relevant Uponor wiring diagrams The strainer collects dirt and its filter can be removed for inspection before connecting the pump. and cleaning. SD0000126...
  • Page 12: Cold Water Meter/ Heat Meter Distance Piece

    Mass flux [kg/h] SI0000286 The thermostat is equipped with a pin that limits the temperature to 60 °C (setting 6). Slide out the limiting pin with a strong wire in axial direction. Uponor Combi Port M-XS Installation and operation manual...
  • Page 13: Differential Pressure Regulator

    230 V AC, 50/60 Hz 0.167 600 0.139 500 0.111 400 0.083 300 0.056 200 0.028 100 DI0000126 Item Description Mass flow rate Pressure loss regulator Preset [no of turns] Out of mass flow zone Uponor Combi Port M-XS Installation and operation manual...
  • Page 14: Maintenance

    (about once per month). At return, let the hot water run for about 5 minutes at start up. The ball valves (B) and (C) should only be closed for assembly/ disassembly reasons. Uponor Combi Port M-XS Installation and operation manual...
  • Page 15: Setting Log Heat Interface Units

    Differential pressure regulator the heating circuit 50-150 mbar 100 mbar Other components/ devices Component Description Type Comment Heat exchanger GBS 220H-16 Plates GKE 228H-24 Plates GKE 228H-40 Plates Installer, signature: Installer, in capital letters: Service partner: Uponor Combi Port M-XS Installation and operation manual...
  • Page 16: Troubleshooting

    Clean the capillary of the differential pressure control, check the differential pressure control is working Air in the system Vent/flush the system Radiator supply Supply flow rate too low / too high Check the zone valve setting Uponor Combi Port M-XS Installation and operation manual...
  • Page 17 Check that the central heating circuit pump is working and correctly set working Central strainer is dirty Clean the central strainer Heating system is not working Check the heating system correctly Buffer storage tank is not filled Check the buffer storage tank filling Uponor Combi Port M-XS Installation and operation manual...
  • Page 18: Technical Data

    106 mm 94 mm ∼495 mm ∼198 mm 200 mm 501 mm 350 mm 93 mm 95 mm 501 mm 201,5 mm 361 mm 405 mm 490 mm 35 mm 116 mm Uponor Combi Port M-XS Installation and operation manual...
  • Page 19: Hydraulic Schemes

    Qn 1,5 of approximately 0,05 bar and other internal/ Operating temperature 5-90 °C external fixtures must be added. Max. operating pressure 10 bar Differential pressure 0,6 bar primary heating Min. pressure tap water 2,5 bar Uponor Combi Port M-XS Installation and operation manual...
  • Page 20 DI0000155 • 19 l/min = 1,00 - 1,20 bar Item Description Primary heating demand in litres/hour (l/h), max. 1000 l/h Return temperature °C Primary heating supply temperatures Tapping capacity in litres/minute (l/min) Uponor Combi Port M-XS Installation and operation manual...
  • Page 21 Primary heating demand in litres/hour (l/h), max. 1000 l/h 1000 l/h Return temperature °C Return temperature °C Primary heating supply temperatures Primary heating supply temperatures Tapping capacity in litres/minute (l/min) Tapping capacity in litres/minute (l/min) Uponor Combi Port M-XS Installation and operation manual...
  • Page 22 Tapping capacity in litres/minute (l/min) Pressure drops including ball valve. Additional pressure drops, e.g. heatmeter with Qn 1,5 of approximately 0,05 bar and other internal/ external fixtures must be added. Domestic hot water side (secondary) DI0000153 Uponor Combi Port M-XS Installation and operation manual...
  • Page 23 Primary heating supply temperatures Tapping capacity in litres/minute (l/min) DI0000159 Item Description Primary heating demand in litres/hour (l/h), max. 1000 l/h Return temperature °C Primary heating supply temperatures Tapping capacity in litres/minute (l/min) Uponor Combi Port M-XS Installation and operation manual...
  • Page 24 Return temperature °C Primary heating demand in litres/hour (l/h), max. Primary heating supply temperatures 1000 l/h Tapping capacity in litres/minute (l/min) Return temperature °C Primary heating supply temperatures Tapping capacity in litres/minute (l/min) Uponor Combi Port M-XS Installation and operation manual...
  • Page 25 Domestic hot water side (secondary) DI0000163 Item Description Primary heating demand in litres/hour (l/h), max. 1000 l/h Return temperature °C Primary heating supply temperatures Tapping capacity in litres/minute (l/min) DI0000154 Uponor Combi Port M-XS Installation and operation manual...
  • Page 26 Primary heating demand in litres/hour (l/h), max. 1000 l/h 1000 l/h Return temperature °C Return temperature °C Primary heating supply temperatures Primary heating supply temperatures Tapping capacity in litres/minute (l/min) Tapping capacity in litres/minute (l/min) Uponor Combi Port M-XS Installation and operation manual...
  • Page 27 Cold water warming 50 K (10-60°C) 65°C 70°C 75°C 80°C 85°C 1000 DI0000166 Item Description Primary heating demand in litres/hour (l/h), max. 1000 l/h Return temperature °C Primary heating supply temperatures Tapping capacity in litres/minute (l/min) Uponor Combi Port M-XS Installation and operation manual...
  • Page 28 Uponor GmbH Industriestraße 56, D-97437 Hassfurt, Germany Uponor reserves the right to make changes, without prior notification, 1143307 v1_12-2023_EN to the specification of incorporated components in line with its policy of www.uponor.com Production: Uponor/ DCO continuous improvement and development.