MQ Power WHISPERWATT DCA125SSIU4F Operation Manual page 55

Hide thumbs Also See for WHISPERWATT DCA125SSIU4F:
Table of Contents

Advertisement

4. Press the TEST button (Figure 80) on the GFCI
receptacle and verify that the status LED turns OFF.
Figure 80. GFCI Receptacle (OFF)
5. Press the RESET button (Figure 81) to restore power
to the GFCI receptacle and verify that the status LED
is ON (GREEN).
Figure 81. GFCI Receptacle (ON/Restore)
6. If the status LED (Figure 82) is flashing (RED),
DO NOT use the GFCI receptacle and replace it
immediately.
Figure 82. GFCI Receptacle (Red Flashing LED)
7. Repeat the above procedure for any other GFCI
receptacles.
DCA125SSIU4F 60 HZ GENERATOR • OPERATION MANUAL — REV. #6 (05/12/22) — PAGE 55
TEST
BUTTON
STATUS
LED (OFF)
RESET
BUTTON
GREEN
STATUS
LED (ON)
RED
STATUS LED
(FLASHING)
GENERATOR STORAGE
For long-term storage of the generator the following is
recommended:
„ Drain the fuel tank completely. Treat with a fuel stabilizer
if necessary.
„ Completely drain the oil from the crankcase and refill if
necessary with fresh oil.
„ Clean the entire generator, internal and external.
„ Cover the generating set and store in a clean, dry place.
„ Disconnect the battery.
„ Make sure engine coolant is at the proper level.
„ If the generator is mounted on a trailer, jack the trailer
up and place it on blocks so the tires do not touch the
ground, or block and completely remove the tires.
MAINTENANCE