Air Filter Dust Indicator
NOTICE
The air filter should not be changed until the indicator
reads RED. Dispose of the old air filter. It may not be
cleaned or reused.
The air filter indicator (Figure 66) is attached to the air
filter. When the air filter element is clogged, air intake
restriction becomes greater and the air filter indicator signal
shows RED. When the indicator is red, replace the filter
immediately. After changing the air filter, press the air filter
indicator button to reset.
PUSH BUTTON TO RESET
Figure 66. Air Filter Dust Indicator
DRAINING THE FUEL FILTER ELEMENT
NOTICE
Inspect the fuel filter daily. If the fuel filter (Figure 67) has
collected a significant amount of water and sediment
at the bottom of the cup, it should be drained off
immediately.
1. Loosen the air bleeder plug (Figure 67) on the fuel
filter body.
2. To discharge the fuel inside the fuel filter, OPEN
the drain valve on the fuel filter by turning the knob
counterclockwise (Figure 67A) approximately
3-1/2 turns until the valve drops down 1 inch (25.4 mm)
and draining occurs (Figure 67B).
DCA125SSIU4F 60 HZ GENERATOR • OPERATION MANUAL — REV. #6 (05/12/22) — PAGE 49
25 INCHES H O
2
6.23 kPa
FILTER BODY
FUEL FILTER
DRAIN PLUG
A
OPEN
Figure 67. Draining Fuel Filter
3. Let the residue or foreign substances inside the case
flow into a suitable container.
4. At completion of draining, CLOSE the drain valve
(Figure 67C).
MAINTENANCE
AIR BLEEDER
PLUG
B
C
CLOSE