MQ Power WHISPERWATT DCA125SSIU4F Operation Manual page 29

Hide thumbs Also See for WHISPERWATT DCA125SSIU4F:
Table of Contents

Advertisement

120 VAC GFCI Receptacles
NOTICE
It is recommended that the GFCI receptacles be tested
when the generator is initially uncrated. The receptacles
should then be tested daily at startup.
There are two 120 VAC, 20-amp GFCI (duplex NEMA
5-20R) receptacles provided on the output terminal panel.
These receptacles can be accessed in any voltage
selector switch position. Each receptacle is protected by a
20-amp circuit breaker. These breakers are located directly
above the GFCI receptacles. Remember the load output
(current) of both GFCI receptacles is dependent on the
load requirements of the U, V, and W output terminal lugs.
Pressing the reset button resets the GFCI receptacle after
being tripped. Pressing the test button (See Figure 14) in
the center of the receptacle will check the GFCI function.
Both receptacles should be tested at least once a month.
RESET
BUTTON
Figure 14. 120 VAC GFCI Receptacle
Twist-Lock Dual-Voltage 240/120 VAC Receptacles
There are three 240/120V, 50-amp, auxiliary twist-lock
(CS-6369) receptacles (Figure 15) provided on the
output terminal panel. These receptacles can only be
accessed when the voltage selector switch is placed in the
single-phase 240/120V position.
CS-6369 TWIST-LOCK
RECEPTACLES
SINGLE-PHASE 240/120 VAC
50 AMP OUTPUT
Figure 15. 240/120V Twist-Lock Auxiliary
Receptacles
DCA125SSIU4F 60 HZ GENERATOR • OPERATION MANUAL — REV. #6 (05/12/22) — PAGE 29
OUTPUT TERMINAL PANEL FAMILIARIZATION
TEST
BUTTON
STATUS
LED
Each auxiliary receptacle is protected by a 50-amp circuit
breaker. These breakers are located directly above the
GFCI receptacles. Remember the load output (current) on
all three receptacles is dependent on the load requirements
of the output terminal lugs.
Voltage Regulator
NOTICE
The voltage regulator (VR) allows the user to increase
or decrease the selected voltage.
Turn the voltage regulator control knob (Figure 16) on
the control panel to obtain the desired voltage. Turning the
knob clockwise will increase the voltage, turning the knob
counterclockwise will decrease the voltage.
DECREASE
Figure 16. Voltage Regulator Control Knob
Removing the Plastic Face Plate
(Hard Wire Hookup Panel)
The Output Terminal Lugs are protected by a plastic face
plate cover (Figure 17). Unscrew the securing bolts and
lift the plastic terminal cover to gain access to the terminal
enclosure.
After the load wires have been securely attached to the
terminal lugs, reinstall the plastic face plate.
PLASTIC
TERMINAL
COVER
Figure 17. Plastic Face Plate
(Output Terminal Lugs)
INCREASE
HARD WIRE
HOOKUP PANEL
SECURING
BOLTS

Advertisement

Table of Contents
loading

Table of Contents