Override Function At Start-Up; Override During Operation Cycle - Omron F3S-TGR-CL-K2C Installation And Operation Manual

Body protection sensor safety light curtain
Table of Contents

Advertisement

Override

11-3-1 Override function at start-up

1
5
> 5 s

11-3-2 Override during operation cycle

1
< 1 s
RESTART
5
< 1 s
RESTART
Note • To start override, the F3S-TGR-CL must be in MACHINE STOP state.
• If the entire protective field is free for more than 2sec. the override function
is immediately stopped.
• A Test request on the TEST/RESTART input will stop the override function
immediately.
• Maximum timeout for override is 600sec. After this timeout, the F3S-TGR-
CL system is restarting according to the interlock mode set by the selector
switches.
Conditions:
• At least one beam of the F3S-TGR-CL system must be blocked
• F3S-TGR-CL system is in MACHINE STOP mode.
2
6
OVERRIDE START.
LMS flashes
Override function is stopped immediately if the TEST/RESTART input is acti-
vated during the Override function.
Conditions
• At least one beam of the F3S-TGR-CL system must be blocked
• F3S-TGR-CL system is in MACHINE STOP mode.
• One or both muting inputs are active.
2
< 1 s
+24VDC
RESTART
6
> 1 s
+24VDC
RESTART
Override function is stopped immediately if the TEST/RESTART input is acti-
vated during the Override function
3
Wait < 5 s
7
To avoid EDM error at
override function end
RESTART
3
< 1 s
+24VDC
RESTART
7
OVERRIDE
START.
+24VDC
LMS flashes
Section 11-3
4
RESTART
8
End of
OVERRIDE
+24VDC
4
< 1 s
+24VDC
RESTART
8
9
> 2 s
End of OVER-
RIDE
+24VDC
9
+24VDC
35