5 SEQUENCE INSTRUCTIONS FOR MOTION CPU
X5
Input conditions
X5
Input conditions
X7
Reset input
(2) 100ms timer (T16 to T95, T144 to T239)
(a) When the input conditions are set, the count starts. When the set value is
counted, that timer contact will turn ON.
(b) If the input conditions are turned OFF, the 100ms timer count value will be
set to 0, and the contact will turn OFF.
(c) The value is set with a decimal (Kn), and can be designated from 1 to 32767
(×0.1[s]). The data register (D) data can also be used as the setting value.
100ms timer
(3) 100ms retentive timer (T96 to T103, T240 to T255)
(a) When the input conditions are set, the count starts. When the set value is
counted, that timer contact will turn ON.
(b) Even the input conditions are turned OFF, the 100ms retentive timer current
value (count value) will be held, and the contact state will not change.
(c) The 100ms retentive timer count value will be set to 0 and the contact will
turn OFF when the RST instruction is executed.
(d) The value is set with a decimal (Kn), and can be designated from 1 to 32767
(×0.1[s]). The data register (D) data can also be used as the setting value.
(e) Current value (counter value) of the 100ms retentive timer at power is 0.
K100
T100
100ms
retentive timer
RST T100
T100
reset instruction
T100 contact
T100 current value 0
X5
K50
T16
T16 coil
5 seconds
T16 contact
X5
9 seconds
X7
T100 coil
9 seconds
1
to
90
5 - 4
1.5 seconds
6 seconds
1 seconds
6 seconds
91 to 100
0
1 to 60