32-Point Sink-Type Transistor Output Unit - Panasonic FP7 Series User Manual

Digital input/output unit
Hide thumbs Also See for FP7 Series:
Table of Contents

Advertisement

2.3 Output Unit Specifications

2.3.4 32-point Sink-type Transistor Output Unit

Description
Items
Insulation system
Output type
Rated load voltage
Allowable load voltage range
Max. load current
Common limits
Max. inrush current
OFF state leakage current
ON state max. voltage drop
Response time
External power
supply
Surge absorber
Short-circuit protection
Input points per common
Operating mode indicator
External connection method
Weight (unit)
Restriction on load current
Refer to the following figure and reduce the load current according to the external power supply
voltage.
2-12
AFP7Y32T
Optical coupler
Open collector
5 to 24 V DC
4.75 to 26.4 V DC
0.3 A (20.4 to 26.4 V DC) and 30 mA (4.75 V DC)
3.2 A/common
0.6A
1 μA or less
0.5 V or less
OFF→ON
0.1 ms or less (Load current: 1 mA or more)
ON→OFF
0.3 ms or less (Load current: 1 mA or more)
Voltage
4.75 to 26.4 V DC
Current
110 mA/common (at 24 V)
Zener diode
None
32 points/common
32-point LED indicator (Lit in ON state)
Connector connections (40P, conforming to MIL standards)
Approx. 95g
WUME-FP7DIO-05

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fp0h series

Table of Contents