Items
Insulation system
Output type
Rated load voltage
Allowable load voltage range
Max. load current
Common limits
Max. inrush current
OFF state leakage current
ON state max. voltage drop
Response time
External power
supply
Surge absorber
Short-circuit protection
Input points per common
Operating mode indicator
External connection method
Weight (unit)
Internal circuit Diagram
WUME-FP7DIO-05
0.3 A specifications
(Y0 to 7)
0.1 A specifications
(other than the above)
OFF→ON
ON→OFF
Voltage
Current
2.4 I/O Mixed Unit Specifications
AFP7XY64D2P
Optical coupler
Open collector
5 to 24 V DC
4.75 to 26.4 V DC
0.3 A (20.4 to 26.4 V DC) and 30 mA (4.75 V DC)
0.1 A (20.4 to 26.4 V DC) and 15 mA (4.75 V DC)
3.2 A/common
0.6A
1 μA or less
0.5 V or less
0.1 ms or less (Load current: 2 mA or more)
0.5 ms or less (Load current: 2 mA or more)
4.75 to 26.4 V DC
90 mA/common (at 24 V)
Zener diode
None
32 points/common
32-point LED indicator (Lit in ON state, switchable)
Connector connections (40P x 2, conforming to MIL
standards)
Approx. 115g