ADTEK CPM-20 Series Operation Manual page 10

Multifunction power meter
Hide thumbs Also See for CPM-20 Series:

Advertisement

Engineers set class, non-personnel do not arbitrarily enter the change,
*
in order to avoid abnormal
INPUT Group
Operation display
Press
Key Enter the setup menus
Password
0000~9999
▼KEY
Default 1000
A 1 -
Voltage Phase line set
Set range is as follows:
1P2W 1P3W 3P3W
/
/
/
3P3W.B(
Balanced)/
3P3W3
3P4W 3P4W.B
/
(Balanced
Default:3P4W
A 2 -
Primary voltage (PT)
Set range
:10
0~500
000V
Default 600
A 3 -
Secondary voltage
Set range 100~ 00
:
6
V
Default:
A 4 -
Primary current (CT)
Set range ~10000A
:1
Default 5 :
:
/
)
:
(PT)
600
9
A 5 -
Secondary current
mode selection
Set range:
5A 1A 333mV
Default:5A
(If default is 333mV, it
cannot be changed)
A 6 -
Watt-h / Var Clear
Clear Passwords:
~
0000 9999
Code:2100
A 7 -
P.COD
Set range:
~
0000 9999
Default:1000
A 8 -
Auto wiring change
◎Additional screen display
for V3.0 and above version
YES / NO
R 485 Group
R 485 Group
S
S
E-1
Communication
station No.
Set range:001~247
Default 1 :