Operating Guide Termix VX with complete insulation
7.0 Troubleshooting
7.1 Troubleshooting in general
In the event of operating disturbances, the following basic features
should be checked before carrying out actual troubleshooting:
•
the substation is connected to electricity,
•
the strainer on the DH supply pipe is clean,
•
the supply temperature of the DH is at the normal level
(summer, at least 60 °C - winter, at least 70 °C),
•
the differential pressure is equal to or higher than the normal
(local) differential pressure in the DH network – if in doubt, ask
the DH plant supervisor,
•
pressure on the system - check the HE pressure gauge.
AQ221686472754en–010401 / LUK4030601
Authorized personnel only
Assembly, start-up and maintenance work must be performed by
qualified and authorized personnel only.
© Danfoss | 2022.11 | 19