Step
4
Click the Function button to access the Calibration Disabled state.
Notice the only change in the screen information shown below is the upper and lower display
lines. This lets you know what step of the calibration process your currently on.
5
Click the Function button to access the Begin Calibration state.
6
Click the Function button to access the POS Output Value Calibration state.
The output value can now be viewed as the sensor adjustment is made. Typical output value =
2.500Vdc when motor position = 50%.
Note: If at any time question marks (?) are observed in both the upper and lower
displays, this is an indication that communications between the PDA and the unit have
been lost. To check communications, see Preparation on page 1.
Release 3
8/02
Action
HercuLink™ - User Manual
HercuLink
Calibration
19