Step
6
Click the Function button to access the Apply Motor Hi Calibration state.
The motor can be positioned to its high limit by using the Incr + 10% as a coarse adjust. Click
it several times to get as close to the actual position desired. Then click the Increment button
to fine-tune the final high calibration point. The motor can also be positioned with the optional
auto/manual switch on the side of the unit, or with the optional handwheel.
Note: If at any time question marks (?) are observed in both the upper and lower
displays, this is an indication that communications between the PDA and the unit have
been lost. To check communications, see Preparation on page 1.
7
Click the Function button to access the Calibration Complete state and to save the calibration.
If the unit was in AUTO mode before calibration was started, it will be placed back into AUTO
mode. If the unit was in MAN mode it will stay in MAN mode. Click Close button to return to
Home page.
Release 3
8/02
Action
HercuLink™ - User Manual
HercuLink
Calibration