Step
7
Click the Function button to access the Apply Span Count Calibration state.
The output voltage can be adjusted up or down by clicking the Incr + 10%, Decr – 10%,
Increment and Decrement buttons. Click any button as many times as necessary to get to the
output voltage level desired. Typically 5.00Vdc for 4_20mA and 0_20mA.
Note: If at any time question marks (?) are observed in both the upper and lower
displays, this is an indication that communications between the PDA and the unit have
been lost. To check communications, see Preparation on page 1.
8
Click the Function button to access the Calibration Complete state and to save the calibration.
If the unit was in AUTO mode before calibration was started, it will be placed back into AUTO
mode. If the unit was in MAN mode it will stay in MAN mode. Click Close button to return to
Home page.
9
Click the Close button to exit the Output Calibration procedure. This will return you to the
Home page.
ATTENTION: If you click Close button without clicking the Function button (see previous step),
the unit will remain in MAN mode. To change to AUTO mode, go to Main menu, Configuration,
Lockout, then select MODE CHG.
Release 3
8/02
Action
HercuLink™ - User Manual
HercuLink
Calibration
17