Flow rate monitor / totalizer with high / low alarms, analog and pulse outputs (48 pages)
Summary of Contents for Fluidwell F111-P
Page 1
F111-P DUAL FLOW RATE INDICATOR / TOTALIZER Signal input flowmeter: pulse, Namur and coil Signal outputs: two pulse outputs ref. total Options: Intrinsically safe, Modbus communication F-Series - Field mounted indicators for safe and hazardous areas. More info: www.fluidwell.com/fseries...
The F111-P must be installed in accordance with the EMC guidelines (Electro Magnetic Compatibility). • Connect a proper grounding to the metal enclosure as indicated if the F111-P has an incoming power or signal line which carries a hazardous live voltage. The Protective Earth (PE) wire may never be disconnected or removed.
This manual describes the standard unit as well as the available options. For additional information, please contact your supplier. A hazardous situation may occur if the F111-P is not used for the purpose it was designed for or is used incorrectly. Please carefully note the information in this manual indicated by the pictograms: A "warning !"...
Page 4 TABLE OF CONTENTS SAFETY INSTRUCTIONS........................2 DISPOSAL OF ELECTRONIC WASTE ....................2 SAFETY RULES AND PRECAUTIONARY MEASURES ..............2 ABOUT THE MANUAL ........................3 WARRANTY AND TECHNICAL SUPPORT ..................3 TABLE OF CONTENTS ........................4 INTRODUCTION ........................6 System description ......................
Page 5
Page 5 5.2.1 General information and instructions ..............33 5.2.2 Installations based on ATEX or IECEx certificate ..........34 Electrical data – Annex 1 ..................35 5.2.3 5.2.4 Power supply wiring .................... 37 5.2.5 Sensor supply ..................... 37 Terminal connectors Intrinsically Safe applications – Type XI ........38 5.3.1 Terminal 26-29: Type CT - Communication ............
1 INTRODUCTION SYSTEM DESCRIPTION Functions and features The dual flow rate / totalizer model F111-P is a microprocessor driven instrument designed to show the flow rate, the total and the accumulated total of two completely separated flow measurement systems. This product has been designed with a focus on: ▪...
Page 7
Page 7 Configuration of the unit The F111-P is designed for use in many types of applications. For that reason, a setup menu is available to program the F111-P according to your specific requirements. The setup includes several important features, such as K-Factors, engineering units, signal selection, power management (to extend battery life-time), etc.
Page 8 2 OPERATIONAL GENERAL INFORMATION This chapter describes the daily use of the F111-P. This instruction is meant for users / operators. • This device may only be operated by persons who are authorized and trained by the operator of the facility. All instructions in this manual are to be observed.
Page 9
Page 9 ▪ Clear total The value for total can be reset. To do so, press the CLEAR/ key twice. When the key is pressed once, the text "PUSH CLEAR" is shown. To avoid a reset at this stage, press another key other than the CLEAR/...
Make sure that the unit is not being used for any application when altering the settings. 3.2.1 ENTERING SETUP-LEVEL Configuration of the F111-P is done at SETUP-level, which can be reached at all times while the F111-P remains fully operational. At SETUP-level the display will deactivate the indicator and...
Page 11 Use the control panel to navigate through SETUP-level PROG-key When a function is selected, this key is used to start the programming sequence. When only a function group is selected (and no function), this key is used to scroll back a function group (e.g.
In order to return to the operator level, press the PROG-key for three seconds. When no keys are pressed for 2 minutes, SETUP-level will be left automatically. CONFIGURATION SETTINGS All settings of the F111-P can be set via the control panel. The following paragraphs give a detailed description of each setting. 3.3.1...
3.3.5 MENU 4 - FLOWRATE B The dual flow rate / totalizer model F111-P has two, completely separated, flowmeter inputs (A and B). Inputs A and B are configured with identical menu’s. For clarity, where applicable for flowmeter A and B, only the explanation for flowmeter A is given. For explanation of Menu 3 - TOTAL B refer to Menu 1 - TOTAL A, and for Menu 4 - FLOWRATE B refer to Menu 2 - FLOWRATE A.
When used with the internal battery option (type PB/PC), the user can expect reliable measurement over a long period of time. The F111-P has several smart power management functions to extend the battery life time significantly. Two of these functions can be set.
Enter this quantity here while taking the decimals for pulse into account. 3.3.10 MENU 9 – PULSE OUTPUT B The dual flow rate / totalizer model F111-P has two, completely separated, flowmeter inputs (A and B). Pulse Outputs A and B are configured with identical menus. For clarity, where applicable for flowmeter A and B, only the explanation for flowmeter A is given.
• The F111-P may only be operated by persons who are authorized and trained by the operator of the facility. All instructions in this manual are to be observed. •...
The F1-Series can be supplied as suitable for Safe Area or Hazardous Area. Suitability for Intrinsic Safety is indicated in the model code by Type XI (e.g. F111-P-XI). For Intrinsically Safe applications: Installation and identification labels are shown in chapter 5.
Page 19 Terminal label Also on the inside, a terminal label is placed to indicate the location of the terminals and settings for the sensor supply configuration switches. Fig. 8: Identification – Example of F1-Series terminal label (safe area) Serial number and year of production The serial number can be reviewed on the identification label or in SETUP-menu Others.
Page 22 4.4.3 MOUNTING The enclosure can be installed by itself or with the aid of a mounting plate in the configurations shown below. When the unit is installed on a wall or onto a meter, please use components and installation techniques that are suitable for the used materials.
Metal enclosure When the F111-P is supplied with a metal enclosure (aluminum or stainless steel), the enclosure must be grounded in accordance with national and local electrical codes.
Within the United States all field wiring must conform to the National Electric Code, NFPA 70, Article 501-4(b). All field wiring enters the F111-P through the bottom of the enclosure and connects to the circuit assembly inside the enclosure. Wiring is routed through cable glands. Please make sure to order the F111-P with the correct drilling pattern and thread (metal) or hole (plastic) sizes.
Setting the sensor supply Risk of electrocution - High voltage! Make sure, all the leads to the terminals are disconnected from the F111-P and NEVER connect mains power to the unit when the protection cover has been removed! To set the sensor supply, follow these instructions: 1.
4.5: Electrical Installation and review paragraph 4.5.3 and 4.5.4 before applying any field or power supply wiring. For Intrinsically Safe applications (Type XI): read chapter 5. Following terminal connectors are available on the F111-P when supplied with Type XX: Fig. 13: Overview of terminal connectors - Standard configuration and options 4.6.1...
Page 27 4.6.2 TERMINAL 03-04: SCALED PULSE OUTPUT (FLOW B) Setup 9 determines the pulse output function for input B. The maximum pulse frequency of this output is 500Hz. If a relay output option has been supplied, be sure that the output frequency does not exceed 5Hz or else the life-time of the relay will be reduced significantly.
(read chapter 3). Sine-wave signal (Coil) The F111-P is suitable for use with flowmeters which have a coil output signal. Two sensitivity levels can be selected: • COIL-LO: sensitivity from about 80mV •...
Page 29
Pulse-signal PNP / PNP-LP The F111-P is suitable for use with flowmeters which have a PNP output signal. 3V is offered on terminal 11 which has to be switched by the sensor to terminal 10 (SIGNAL). For a reliable pulse detection, the pulse amplitude has to go above 1.2V.
Fig. 21: Terminal connections - Reed-switch signal input (typical) NAMUR-signal The F111-P is suitable for flowmeters with an Namur signal. The standard F111-P is not able to power the Namur sensor, as an external power supply for the sensor is required. However, a 8.2V sensor supply voltage (terminal 11) can be provided with power supply type PD, PF, PM.
Page 31 4.6.6 TERMINAL 26-31: TYPE CB / CH / CI - COMMUNICATION (OPTION) Serial communications on hardware layers RS232, RS485 and TTL (intrinsic safety) are possible. Make sure that the hardware layer specific requirements are met to achieve reliable communication and read the Modbus communication protocol and Appendix C.
The F1-Series can be supplied as suitable for Safe Area or Hazardous Area. Suitability for Intrinsic Safety is indicated in the model code by Type XI (e.g. F111-P-XI). If Type XI is not indicated your device is not suitable for Intrinsically Safe applications!
Page 33 Terminal label Also on the inside, a terminal label is placed to indicate the location of the terminals and settings for the sensor supply configuration switches. Fig. 26: Identification – Example of F1-Series terminal label (intrinsic safety) ELECTRICAL INSTALLATION IN HAZARDOUS AREA 5.2.1 GENERAL INFORMATION AND INSTRUCTIONS Cautions...
Page 34 5.2.2 INSTALLATIONS BASED ON ATEX OR IECEX CERTIFICATE Installation instructions • For installation under ATEX directive: this Intrinsically Safe device must be installed in accordance with ATEX directive 2014/34/EU and product certificate KEMA 03ATEX1074 X. • For installation under IECEx scheme: this Intrinsically Safe device must be installed in accordance with product certificate IECEx DEK 11.0042X.
Page 35 ELECTRICAL DATA – ANNEX 1 5.2.3 Annex 1 (model specific) to type XI product certificates KEMA 03ATEX1074 X, IECEx DEK 11.0042X For the combined connection of the different supply, input and output circuits, the installation instructions of the manufacturer shall be observed. From the safety point of view the circuits shall be considered to be connected to earth.
Page 36
Page 36 Coil, Switch, PNP, NAMUR In type of protection intrinsic safey Ex ia IIB/IIIC or Ex ia IIC, in combination inputs with connected external supply input type -PD, with following maximum values: (terminals 10 and 11, 8.7 V Ex ia IIB/IIIC Ex ia IIC terminals 13 and 14) 25 mA...
The following types of power supply are available for hazardous area: • Type PX / PD As standard, the F111-P is supplied with terminal 0 and 1 to power the product externally. Additionally, the power supply circuit connected to terminal 1 is looped through to terminal 2 to allow easy installation, e.g.
4. Normally, the F111-P-XI is classified as group IIB/IIIC. Classification of the unit as group IIC is possible under certain conditions, as shown in Annex 1 in the previous paragraph.
Repairs should only be carried out by the manufacturer or his authorized agent. Repair policy If you have any problem with your Fluidwell product and you wish to repair it, please follow the procedure below: a. Obtain a Return Material Authorization (RMA) from your supplier or distributor Together with the RMA, you need to complete a repair form to submit detailed information about the problem.
Page 42 BATTERY REPLACEMENT INSTRUCTIONS 6.3.1 SAFETY INSTRUCTIONS • Handle the battery with the utmost care to prevent a short circuit and damage. A mistreated battery can become unsafe. Unsafe batteries can cause (serious) injury to persons. Do not recharge, crush, disassemble, incinerate, heat above its rated temperature or expose contents to water.
Page 43 6.3.2 REPLACE THE BATTERY Before starting the battery replacement procedure, make sure that the marking on the new battery corresponds with the type of installation, as shown in paragraph 6.3.1. Remove the old battery as follows: 1. Open the enclosure as indicated in section 4.3 and carefully remove the cable-connectors. 2.
Page 44 APPENDIX A TECHNICAL SPECIFICATION General Display Type High intensity numeric and alphanumeric LCD, UV-resistant. Digits Seven 17mm (0.67") and eleven 8mm (0.31"). Various symbols and measuring units. Refresh rate User definable: 8 times/sec - 30 secs. Type ZB LCD with LED backlight.
Page 45
Page 45 Power supply Type PB Standard lithium battery - life-time depends upon settings - up to 5 years. SAFE AREA ONLY Type PC Intrinsically Safe lithium battery - life-time depends upon settings - up to 5 years. Type PD 8-24V AC / 8-30V DC;...
Page 46
Page 46 Inputs Flowmeter Type P npn; npn-lp; reed; reed-lp; pnp; pnp-lp; namur; coil-hi; coil-lo; 8-1 DC; 12 DC; 24 DC Frequency Minimum 0 Hz - maximum 7 kHz for total and flow rate. Maximum frequency depends on signal type and internal low-pass filter. E.g.
Page 47 APPENDIX B PROBLEM SOLVING In this appendix, several problems are included that can occur when the F111-P is going to be installed or while it is in operation. Flowmeter does not generate pulses: Check: ▪ Signal selection; ▪...
Page 48 APPENDIX C COMMUNICATION VARIABLES General The product is fitted with the Modbus communication protocol and can be equipped with various physical interfaces like RS485 and RS232 (please see device datasheet for available options). The tables below show the various variables that can be accessed through the communication. Currently, the function codes supported are: •...
Page 49
Page 49 * Clearing total: It is possible to clear the total counter by means of writing a value of 0 to all the 3 registers of total/flow rate in a single write action. Writing any other value will result in the reply of an error message because the registers of total/flow rate are during operation read-only.
Page 50
Page 50 [d] 232 40233 cut-off time uint16 1...9999 [h] 0x0E8 Representation: 0.1 – 999.9 sec REGISTER VARIABLE TYPE VALUE / REMARKS ADDRESS DISPLAY REGISTERS [d] 64 40065 display function uint16 0=total 1=flow rate [h] 0x040 [d] 65 40066 accumulated total uint16 0=disable 1=enable [h] 0x041...
Page 51
Page 51 REGISTER TYPE VALUE / REMARKS VARIABLE ADDRESS OTHERS REGISTERS [d] 173 40174 model number uint16 0…9999 [h] 0x0AD [d] 160 40161 model suffix char Representation: ASCII character [h] 0x0A0 [d] 162 40163 firmware version uint32 0…999999 [h] 0x0A2 Representation: nn:nn:nn [d] 165 40166...
February e, Fluidwell , declare under our sole responsibility that the F eries indicators are designed and will operate conform the following applicable uropean Directives and Harmonised tandards, when installed and operated according to the related manuals:...
Page 55
Page 55 LIST OF CONFIGURATION SETTINGS SETTING DEFAULT DATE : DATE : 1 – TOTAL-A Enter your settings here 1.1 unit 1.2 decimals 0000000 1.3 K-Factor 0000001 1.4 decimals K-Factor 2 - FLOW RATE 2.1 unit 2.2 time /min 2.3 decimals 0000000 2.4 K-Factor 0000001...