Repair
40
Order number
Device type
• 71125436
FDR56-IA1A****, F15 (datecode up to 04.2016)
• 71324380
FDR56-IA1A****, F15 (datecode from 05.2016)
• 71324382
FDR56-IA1A****, F34
• 71125437
FDR56-IA1E****, F15 (datecode up to 04.2016)
• 71324381
FDR56-IA1E****, F15 (datecode from 05.2016)
• 71324383
FDR56-IA1E****, F34
• 71125438
FDR56-IA2A****, F15
• 71324387
FDR56-IA2A****, F34
• 71125439
FDR56-IA2E****, F15
• 71324388
FDR56-IA2E****, F34
• 71125440
FDR56-IA3A****, F15
• 71324389
FDR56-IA3A****, F34
• 71125441
FDR56-IA3E****, F15
• 71324390
FDR56-IA3E****, F34
• 71125421
FQR56-IAA****, F15
• 71324250
FQR56-IAA****, F34
• 71125422
FQR56-IAE****, F15
• 71324252
FQR56-IAE****, F34
11�4�2

Replacing the electronics

32 Replacing the electronics
1
Electronics
2
Screw
3
Spacers
The electronics are mounted on two self-clamping spacers and secured with a screw:
Loosen the screw.
PH2
Detach the electronic insert by pulling it from the two spacers and take it out of the
device vertically.
Insert the new electronic insert straight into the housing, push it onto the spacers to
snap it in and fasten it with the screw (1 to 2 Nm).
11�5

Return

The measuring device must be returned if the wrong device has been ordered or delivered.
As an ISO-certified company and also due to legal regulations, Endress+Hauser is obli-
ged to follow certain procedures when handling any returned products that have been in
contact with medium. To ensure safe, swift and professional device returns, please refer
to the procedure and conditions for returning devices provided on the Endress+Hauser
website at
http://www.endress.com/support/return-material
Soliwave FDR56/FQR56