Operation options
28
When operating several microwave barriers installed close to each other, the Soliwave
FDR57/FQR57 device combination with the FTR525 Nivotester should be selected; with
this, independent parallel operation is possible.
7.2

On-site operation

7.2.1

Operation of the FDR56

Select any function (Overview → 35)
→ Encoding switch 1 to F
...
0
0
→ The display shows the selected function 1 to F for two seconds.
...
Setting the selected function
→ The two operating buttons can be used to increase/decrease the value or to switch
the selection.
Example: Function 3 (manual adjustment on free path)
...
The configured value is stored as soon as the function is switched.
→ The value can be displayed again at any time by selecting the corresponding para-
meter configuration function and changed if necessary.
After the parameterization has been completed (i.e. after the microwave barrier has
been adapted to the respective medium), the encoding switch must be returned to the
"0" position and the FDR56 is now ready for operation.
7.2.2

Operation of the FQR56

Selection of the switch position 0 to 4 (slightly different operating frequency in each
case)
0
...
0
Select the next switch position if the interference is still present.
The switch positions 5 to F have no function, the operating frequency in these posi-
tions corresponds to switch position 0.
7.3

Parameterization

The microwave barrier can be adjusted on the FDR56. The setup can be made on free or
covered path. Therefore there are functions for automatic and manual setup available.
For most applications the automatic setup is sufficient.
7.3.1

Adjustment with free or minimum covered path (function 1)

This automatic setup function can be used if the path is free or minimum covered.
Set encoding switch to Position 1
→ Display of the function number
→ After 2 seconds: Display of the current signal strength, example:
oder
...
Soliwave FDR56/FQR56
Endress+Hauser