NOTE
• When using stranded wires without a crimp terminal, twist enough to avoid short circuit with a nearby terminals or wires.
• Pulling out the wire forcefully without pushing the open/close button all the way down may damage the terminal block.
• Use a small flathead screwdriver (tip thickness: 0.4 mm/tip width: 2.5 mm). If a flathead screwdriver with a narrow tip is
used, terminal block may be damaged.
Commercially available products (as of October 2020. The product may be changed without notice.)
Product
Model
name
Screwdriver
SZF 0- 0,4 × 2,5
• Place the flathead screwdriver vertical to the open/close button. In case the blade tip slips, it may cause an inverter damage
or injury.
• When wiring cables to the inverter's RS-485 terminals while a plug-in option is mounted, take caution not to let the cables
touch the circuit board of the option or of the inverter. Otherwise, electromagnetic noises may cause malfunctions.