H-System – Isolated Barriers and Termination Boards

Technical Specifications

7
Technical Specifications
7.1

Technical Data

Electrical Data
Power Supply to the Isolated Barriers
19 V DC to 30 V DC
Note
See corresponding datasheets for possible exceptions.
The voltage drop on the termination board via the decoupling diodes must be considered.
Each isolated barrier is internally protected. The termination boards have redundant
power supply connections with fuses that can be replaced by the customer.
Non-Hazardous Area Signals or Control Circuit Signals
0/4 mA to 20 mA signal level according to NE 43
0/2 V to 10 V signal level according to NE 43
0/1 V to 5 V signal level according to NE 43
Current output HART compatible
Current input HART compatible
Digital output: active or passive electronic output 100 mA/30 V, short-circuit protected
Relay output 2 A, minimum load 1 mA/24 V
Logic level 24 V according to IEC 60946
Functional isolation or safe isolation according to IEC 61140 and NAMUR NE 23
Hazardous Area Signals or Signals in the Field Circuit
Transmitter power supply up to 17 V DC
Current output HART compatible
Pt100, 2-, 3-, (4)-wire technology
Resistor 0  to 400  with freely definable characteristic
Potentiometer
Thermocouples of all types, internal cold junction, external reference
Current output HART compatible
Digital input according to NAMUR EN 60947-5-6
Digital output for standard Ex-i valves, short circuit-protected
Characteristic Safety Values
MTBF: Mean Time Between Failures
35