Page 1
User Manual PF 1 6K/10K Online UPS Uninterruptible Power Supply System Version: 1.2...
Page 2
Please comply with all warnings and operating instructions in this manual strictly. Save this manual properly and read carefully the following instructions before installing the unit. Do not operate this unit before reading through all safety information and operating instructions carefully.
Table of Contents 1. SAFETY AND EMC INSTRUCTIONS ....................1 1-1. T ....................... 1 RANSPORTATION AND TORAGE 1-2. P ............................1 REPARATION 1-3. I ............................1 NSTALLATION 1-4........................ 2 ONNECTION ARNINGS 1-5. O ............................3 PERATION 1-6. S ............................3 TANDARDS 2.
1. Safety and EMC instructions Please read carefully the following user manual and the safety instructions before installing the unit or using the unit! 1-1. Transportation and Storage Please transport the UPS system only in the original package to protect against shock and impact.
1-4. Connection Warnings • In accordance with safety standard EN-IEC 62040-1, installation has to be provided with a《Backfeed Protection》 system, as for example a contactor, which will prevent the appearance of voltage or dangerous energy in the input mains during a mains fault. There is no standard backfeed protection inside of the UPS.
• Use of this equipment in life support applications where failure of this equipment can reasonably be expected to cause the failure of the life support equipment or to significantly affect its safety or effectiveness is not recommended. Do not use this equipment in the presence of a flammable anesthetic mixture with air, oxygen or nitrous oxide.
2. Installation and Operation There are two different types of online UPS: standard and long-run models. Please refer to the following model table. Model Type Model Type 6K/6KRT 6KL/6KRTL standard model Long-run model 10K/10KRT 10KL/10KRTL We also offer optional parallel function for these two types by request. The UPS with parallel function is called as “Parallel model”.
Page 8
RT Model Diagram 1: UPS Rear Panel Diagram 2: 2U battery pack Diagram 3: 3U battery pack 1) Share current port (only available for parallel model) 2) Parallel port (only available for parallel model) 3) External battery connector 4) Intelligent slot 5) RS-232 communication port 6) USB communication port 7) Emergency power off function connector (EPO connector)
2-3. Rack/Tower Installation (only for RT model) 2-3-1 Tower Installation The UPS system is shipped with two sets of feet and 6 extensions (2 short extensions plus 4 long extensions) that can be used to tower install the UPS module in 2U or UPS module with one battery bank in 4U. Install UPS module in 2U Assemble two feet as one tower stand shown in step 1.
2-3-2 Rack Installation Please follow below steps to mount UPS into 19” rack or rack enclosure. Step 1: Attach mounting ears to the side mounting Chart 1 holes of UPS using the screws provided and the ears should face forward. Please refer to chart 1. Step 2: Lift the UPS module and slide it into rack Chart 2 enclosure.
Page 11
Remove the terminal block cover on the rear panel of UPS. Then connect the wires according to the following terminal block diagrams: (Connect the earth wire first when making wire connection. Disconnect the earth wire last when making wire disconnection!) Input Neutral Output Line Input Line...
● Make sure the protective earth ground wiring is correct. The wire current spec, color, position, connection and conductance reliability should be checked carefully. ● Make sure the utility input & output wiring is correct. The wire current spec, color, position, connection and conductance reliability should be checked carefully.
Diagram 3: Power cable connection for RT model Diagram 4: Wiring diagram of parallel system for RT model 2-6. Software Installation For optimal computer system protection, install UPS monitoring software to fully configure UPS shutdown.
3. Operations 3-1. Button Operation Button Function Turn on the UPS: Press and hold the button more than 0.5s to turn on the UPS. ON/Enter Button Enter Key: Press this button to confirm the selection in setting menu. ...
Page 15
LCD Panel: Display Function Backup time information Indicates battery discharge time in numbers. H: hours, M: minutes, S: seconds Fault information Indicates that the warning and fault occurs. Indicates the fault codes, and the codes are listed in details in section 3-9. Mute operation Indicates that the UPS alarm is disabled.
3-3. Audible Alarm Description Buzzer status Muted UPS status Bypass mode Beeping once every 2 minutes Battery mode Beeping once every 4 seconds Fault mode Beeping continuously Warning Overload Beeping twice every second Others Beeping once every second Fault Beeping continuously 3-4.
Page 17
total loads connected to the UPS less than 80% of its nominal power capacity to prevent overload for system safety. 5) If the overload time is longer than acceptable time listed in spec at AC mode, the UPS will automatically transfer to Bypass mode. After the overload is removed, it will return to AC mode. If the overload time is longer than acceptable time listed in spec at Battery mode, the UPS will become fault status.
Page 18
the input breaker. A few seconds later, there is no display shown on the display panel and UPS is complete off. 3-4-8. Turn off the UPS without utility power supply in Battery mode 1) Turn off the UPS by pressing “OFF” button for at least 0.5s, and then the buzzer will beep once. 2) Then UPS will cut off power to output and there is no display shown on the display panel.
3-5. Parallel Operation 3-5-1. Parallel system initial startup First of all, please make sure all of the UPSs are parallel models and have the same configuration. 1) Turn on each UPS to AC mode respectively (Refer to section 3-4-1). Then, measure the output voltage of each UPS to check if the voltage difference between actual output and setting value is less than 1.5V (typical 1V) with multimeter.
2) Turn off the output breaker of this unit, and then turn off the input breaker of this unit. 3) After it shuts down, you can turn off the battery breaker (for long-run model) and remove the parallel cable and share current cable. Then, remove the unit from the parallel system. Second method: 1) If the bypass is abnormal, you can not remove the UPS without interruption.
3-7. LCD Setting Parameter 1 Parameter 2 There are two parameters to set up the UPS. Parameter 1: It’s for program alternatives or setting options. Refer to below table. Parameter 2 is the setting values for each program. Programs available list for parameter 1: Bypass/ Battery Code...
Page 22
02: Output frequency Interface Setting 60 Hz, CVCF mode Parameter 2: Output Frequency Setting the output frequency. You may choose following three options in parameter 2: 50CF: Setting UPS to CVCF mode and output frequency will be fixed at 50Hz. The input frequency could be from 46Hz to 64Hz. 60CF: Setting UPS to CVCF mode and output frequency will be fixed at 60Hz.
Page 23
04: Frequency range for bypass Interface Setting Parameter 1 & 2: Setting acceptable frequency range for bypass mode. You have to set up the range by setting high and low points. When it shows “LLS” in parameter 2, please press “Enter”...
Page 24
07: Frequency range for ECO mode Interface Setting Parameter 1 & 2: Setting acceptable frequency range for ECO mode. You have to set up the range by setting high and low points. When it shows “LLS” in parameter 2, please press “Enter” key and it will show “LS”...
Page 25
10: Reserved Interface Setting Reserved 11: Reserved Interface Setting Reserved 12: Hot standby function enable/disable Interface Setting Parameter 2: HS.H Enable or disable Hot standby function. You may choose following two options in Parameter 2: YES: Hot standby function is enabled. It means that the current UPS is set to host of the hot standby function, and it will restart after AC recovery even without battery connected.
Page 26
14: Charger voltage adjustment Interface Setting After it shows “14” in parameter 1, please press “Enter” key first. Then, you may choose Ad or SU to adjust charger voltage in parameter 1 by pressing “Up” or “Down” key. After pressing “Enter”...
17: Charging current setting Interface Setting Parameter 2: Set the charging current of the charger at 1A, 2A, 3A or 4A (001 ~ 004). Parameter 3: Calibrate the charging current. If there is deviation between setting current and real measured current, please use this parameter to calibrate the charging current.
Page 28
LCD display CVCF mode Description When input frequency is within 46 to 64Hz, the UPS can be set at a constant output frequency, 50 Hz or 60 Hz. The UPS will still charge battery under this mode. LCD display Battery mode Description When the input voltage is beyond the acceptable range or power failure, UPS will backup power from battery and alarm will beep every 4 seconds.
LCD display Battery Test Description When UPS is in AC mode or CVCF mode, press “Test” key for more than 0.5s. Then the UPS will beep once and start “Battery Test”. The line between I/P and inverter icons will blink to remind users. This operation is used to check the battery status.
Inverter current detection None Bus voltage changes too fast None error Transformer over temperature None SPS 12V abnormal None 3-10. Warning Indicator Warning Icon (flashing) Alarm Battery low Beeping every second Overload Beeping twice every second Battery unconnected Beeping every second Over charge Beeping every second EPO enable...
4. Trouble Shooting If the UPS system does not operate correctly, please solve the problem by using the table below. Symptom Possible cause Remedy No indication and alarm in the front The AC input power is not Check if input cable firmly display panel even though the mains is connected well.
5. Storage and Maintenance 5-1. Storage Before storing, charge the UPS at least 7 hours. Store the UPS covered and upright in a cool, dry location. During storage, recharge the battery in accordance with the following table: Storage Temperature Recharge Frequency Charging Duration -25°C - 40°C Every 3 months...
6. Specifications Tower Model MODEL 10KL CAPACITY* 6000 VA / 6000 W 10000 VA / 10000 W INPUT 110 VAC(L-N) ± 3 % at 0-60% Load Low Line Loss 176 VAC(L-N) ± 3 % at 60%-100% Load Voltage Range Low Line Comeback Low Line Loss Voltage + 10V High Line Loss 300 VAC(L-N) ±...
Page 34
RT Model MODEL 6KRT 6KRTL 10KRT 10KRTL CAPACITY* 6000 VA / 6000 W 10000 VA / 10000 W INPUT 110 VAC(L-N) ± 3 % at 0-60% Load Low Line Loss 176 VAC(L-N) ± 3 % at 60%-100% Load Voltage Range Low Line Comeback Low Line Loss Voltage + 10V High Line Loss...
Need help?
Do you have a question about the PF 1 6K and is the answer not in the manual?
Questions and answers