Error code
Decimal
Hexadec
imal
-328
FEB8H
-329
FEB7H
-330
FEB6H
-331
FEB5H
-332
FEB4H
-335
FEB1H
-336
FEB0H
-340
FEACH
-342
FEAAH
-343
FEA9H
-344
FEA8H
-345
FEA7H
-350
FEA2H
-351
FEA1H
*1 Can be checked with 'Module label ID' (SD1596 to 1597). (MELSEC iQ-R C Controller Module User's Manual)
*2 Can be checked with a header file used in user programs.
234
Description
Group No. specification error
The specified group number is out of range.
Link time specification error
The specified link scan time is out of range.
Number of detections of disconnected slave stations error
The specified number of detections of disconnected slave
stations is out of range.
CC-Link IE Field Network Basic parameter unset
The function is executed without setting CC-Link IE Field
Network Basic parameters.
Slave station timeout time specification error
Assurance of link scan data waiting time timed out
The specified waiting time elapsed.
Slave station number specification error
The specified slave station number does not exist in the
slave station.
Incorrect password
The specified password for removing the prohibition on the
firmware update is incorrect.
Number of characters exceeded
The number of characters in the specified password for
removing the prohibition on the firmware update is out of the
range.
Unavailable character in password
Unavailable character is specified for the password for
removing the prohibition on the firmware update.
Firmware update enabled
Firmware update prohibition is removed while the firmware
update is not prohibited.
Firmware update prohibited
Firmware update is prohibited again while the firmware
update has already been prohibited.
Module label ID mismatch error
The specified module label ID and the module label ID
written to a C Controller module are different.
Module label error
The specified module label does not exist.
Corrective action
Check the specified group number.
Check the specified link scan time.
Check the specified number of detections of disconnected slave
stations.
Set the CC-Link IE Field Network Basic parameters with CW
Configurator.
Check the timeout time for the disconnection detection of the
specified slave station.
Increase the timeout time specified to the argument.
Check the specified slave station number.
Check the specified password for removing the prohibition on the
firmware update.
Check the number of characters in the specified password for
removing the prohibition on the firmware update.
Check the specified password for removing the prohibition on the
firmware update.
No action is required because the firmware update is enabled.
When changing a password, remove the prohibition on the firmware
update, and then execute the function again.
*1
Check that the module label ID
written to a C Controller module
*2
and the specified module label ID
For how to use module labels, refer to the following:
MELSEC iQ-R C Controller Module User's Manual
Specify the module label (public label) written to the C Controller
module.
match.