Mitsubishi Electric MELSEC iQ-R C Series Programming Manual page 234

Controller module
Table of Contents

Advertisement

Error code
Decimal
Hexadec
imal
-290
FEDEH
-291
FEDDH
-292
FEDCH
-293
FEDBH
-295
FED9H
-296
FED8H
-297
FED7H
-298
FED6H
-299
FED5H
-300
FED4H
-301
FED3H
-302
FED2H
-303
FED1H
-304
FED0H
-305
FECFH
-306
FECEH
-307
FECDH
-308
FECCH
232
Description
MODE is being selected by switch operation
The CCPU_SetOpSelectMode function or the
CCPU_SetDotMatrixLED function was executed while an
operation was being selected with the MODE/SELECT
switch.
Fixed cycle communication area unreserved error
An attempt was made to access a CPU module in which
fixed cycle communication area is not reserved.
Program memory shutdown error
The shutdown processing of the program memory failed.
Data memory shutdown error
The shutdown processing of the data memory failed.
Selected operation is being checked
The CCPU_SetDotMatrixLED function was executed while
checking the selected operation.
Setting data size error
The setting data size is out of range.
Input/output number, network number incorrect
specification
An input/output number out of the range (other than 000H to
FFFH or 3E0H to 3E3H) was specified.
Input/output number, network number incorrect
specification
An input/output number with no module was specified.
Input/output number, network number incorrect
specification
• An input/output number of a module which does not
support the function was specified.
• The dedicated instruction was specified with the specified
module or mode.
Input/output number, network number incorrect
specification
An input/output number of a module, that cannot be
specified, was specified.
Input/output number, network number incorrect
specification
A network number out of the range (other than 1 to 239)
was specified.
Input/output number, network number incorrect
specification
A network number which does not exist was specified.
Input/output number, network number incorrect
specification
An I/O module or intelligent function module controlled by
other CPU modules was specified.
Input/output number, network number incorrect
specification
The target module cannot be identified with a function to
specify an I/O module or intelligent function module.
(The character strings to specify the target module are
incorrect.)
Input/output number, network number incorrect
specification
The specified I/O module or intelligent function module is in
the state where it cannot execute the function.
Device, buffer memory incorrect specification
The specified device exceeded the usable range.
Device, buffer memory incorrect specification
A device that cannot be specified was specified.
Program fault
The specified argument structure is incorrect.
Corrective action
Execute the function after selecting an operation.
Use the fixed cycle communication function in the multiple CPU
setting of system parameter, and check if 1K word or more is set for
the fixed cycle communication area.
• Check if files in the program memory are being accessed.
• Check if all files in the program memory have been closed.
• Check if files in the data memory are being accessed.
• Check if all files in the data memory have been closed.
Execute the CCPU_SetDotMatrixLED function after checking the
operation.
Check the setting data size.
Correct the argument of the function.
• Check if the function is executable for the module corresponding
to the input/output number and network number which are
specified when executing the function.
• Check the applicability of the dedicated function (such as the
support status and executable mode) by referring to the manual
for relevant modules.
Correct the argument of the function.
• Correct the argument of the function.
• Delete a module controlled by other CPU modules, which has
been specified by the link direct device, from the program.
• Specify the network module controlled by the host CPU module
with a link direct device.
Correct the argument of the function.
The possible cause is a hardware failure of the I/O module or
intelligent function module specified. Please consult your local
Mitsubishi representative.
Correct the argument of the function.
Correct the argument of the function.
• Correct the argument of the function.
• Check if the firmware version of the C Controller module supports
the dedicated instruction specified in the program.