Error code
Description
Decimal
Hexadec
imal
Program fault
-309
FECBH
The specified number of devices is incorrect.
-310
FECAH
Operation error
An unusable character string for a function is specified.
Operation error
-311
FEC9H
Data out of the specifiable range was entered.
-312
FEC8H
Operation error
The CCPU_DedicatedDInst function was executed in the
state where the fixed cycle communication function is set to
"Not Use" in the multiple CPU setting of system parameters.
Operation error
-313
FEC7H
In a multiple CPU system, the number of data points which
exceeds the usable system area size in each CPU was
specified.
Module major error
-314
FEC6H
An error was detected in the intelligent function module
-315
FEC5H
when a function was executed.
Other CPU module major error
-316
FEC4H
An error was detected in other CPU modules when a
-317
FEC3H
function was executed.
System bus error
-318
FEC2H
An error was detected on the system bus.
Hardware failure
-319
FEC1H
A hardware failure was detected.
Clock rate specification error
-320
FEC0H
The specified clock rate is out of range.
System bus error
-321
FEBFH
An error was detected on the system bus.
System bus error
-322
FEBEH
An error was detected on the system bus.
-323
FEBDH
System bus error
An error was detected on the system bus.
System bus error
-324
FEBCH
An error was detected on the system bus.
-325
FEBBH
System bus error
An error was detected on the system bus.
System bus error
-326
FEBAH
-327
FEB9H
Module major error
• A major error was notified from the intelligent function
module.
• The I/O module or intelligent function module is not
mounted properly or was removed during operation.
Corrective action
Correct the argument of the function.
Correct the argument of the function.
Correct the argument of the function.
Change the fixed cycle communication function in the multiple CPU
setting to "Use".
Correct the number of data points for the CCPU_DedicatedDInst
function.
The possible cause is a hardware failure of the intelligent function
module where the error was detected. Please consult your local
Mitsubishi representative.
Reset the CPU module. If the same error code is displayed again,
the possible cause is a hardware failure of the host CPU module or
other CPU modules where the error was detected. Please consult
your local Mitsubishi representative.
• Take measures to reduce noise.
• Reset the CPU module. If the same error code is displayed again,
the possible cause is a hardware failure of the CPU module, I/O
module, intelligent function module, base unit, or extension cable.
Please consult your local Mitsubishi representative.
• Take measures to reduce noise.
• Reset the CPU module. If the same error code is displayed again,
the possible cause is a hardware failure of the CPU module.
Please consult your local Mitsubishi representative.
Check the specified clock rate.
• Take measures to reduce noise.
• Reset the CPU module. If the same error code is displayed again,
the possible cause is a hardware failure of the CPU module.
Please consult your local Mitsubishi representative.
• Check the connection status of the extension cable.
• Take measures to reduce noise.
• Reset the CPU module. If the same error code is displayed again,
the possible cause is a hardware failure of the CPU module.
Please consult your local Mitsubishi representative.
• Take measures to reduce noise.
• Reset the CPU module. If the same error code is displayed again,
the possible cause is a hardware failure of the CPU module.
Please consult your local Mitsubishi representative.
• Take measures to reduce noise.
• Reset the CPU module. If the same error code is displayed again,
the possible cause is a hardware failure of the CPU module.
Please consult your local Mitsubishi representative.
• Take measures to reduce noise.
• Reset the CPU module. If the same error code is displayed again,
the possible cause is a hardware failure of the CPU module.
Please consult your local Mitsubishi representative.
• Take measures to reduce noise.
• Reset the CPU module. If the same error code is displayed again,
the possible cause is a hardware failure of the CPU module.
Please consult your local Mitsubishi representative.
• Check the connection status of the extension cable.
• Reset the CPU module. If the same error code is displayed again,
the possible cause is a hardware failure of the CPU module.
Please consult your local Mitsubishi representative.