Summary of Contents for SIGMATEK SDI 101

  • Page 1 SDI 101 S-DIAS Safety Digital Input Module Instruction Manual Date of creation: 18.12.2013 Version date: 05.12.2023 Article number: 20-891-101-E...
  • Page 2 (print, photocopy, microfilm or in any other process) without the express permission. We reserve the right to make changes in the content without notice. The SIGMATEK GmbH & Co KG is not responsible for technical or printing errors in the handbook and assumes no responsibility for damages that occur through use...
  • Page 3 Safety System Handbook, see homepage To use the SDI 101 in an application, a Safety CPU module that regulates the synchronized communication with the safety modules using safe bus telegrams is also required. This also includes •...
  • Page 4: Table Of Contents

    SDI 101 S-DIAS SAFETY DIGITAL INPUT MODULE Contents Introduction ................5 Target Group/Purpose of this Operating Manual ...... 5 Important Reference Documentation ......... 5 Contents of Delivery ..............5 Basic Safety Guidelines ............6 Symbols Used ................6 Disclaimer ..................8 General Safety Directives ............
  • Page 5 S-DIAS SAFETY DIGITAL INPUT MODULE SDI 101 Technical Data ............... 19 Input Specifications ..............19 Signal Output Specifications for Cross-Circuit Detection ..20 Electrical Requirements ............. 20 Input Circuit ................. 22 Miscellaneous ................22 Environmental Conditions ............23 Mechanical Dimensions ............24 Connector Layout ..............
  • Page 6 SDI 101 S-DIAS SAFETY DIGITAL INPUT MODULE 12 Maintenance ................34 12.1 Service ..................34 12.2 Repair ................... 34 13 Disposal ..................34 Page 4 05.12.2023...
  • Page 7: Introduction

    Please see our website for our hotline number and business hours. Important Reference Documentation • Safety System Handbook This and additional documents can be downloaded from our website or obtained through support. Contents of Delivery 1x SDI 101 05.12.2023 Page 5...
  • Page 8: Basic Safety Guidelines

    SDI 101 S-DIAS SAFETY DIGITAL INPUT MODULE Basic Safety Guidelines Symbols Used The following symbols are used in the operator documentation for warning and danger messages, as well as informational notes: DANGER Danger indicates that death or serious injury will occur, if the specified measures are not taken.
  • Page 9 S-DIAS SAFETY DIGITAL INPUT MODULE SDI 101 CAUTION Danger for ESD-sensitive components. Les signes de danger pour les composants sensibles aux décharges électrostatiques. INFORMATION Information  Provides important information on the product, handling or relevant sections of the documentation, which require attention.
  • Page 10: Disclaimer

    It does not guarantee properties under the warranty. Please thoroughly read the corresponding documents and this operating manual before handling a product. SIGMATEK GmbH & Co KG is not liable for damages caused through, non-compliance with these instructions or applicable regulations.
  • Page 11: General Safety Directives

    S-DIAS SAFETY DIGITAL INPUT MODULE SDI 101 General Safety Directives The Safety Directives in the other sections of this operating manual must be observed. These instructions are visually emphasized by symbols. INFORMATION According to EU Directives, the operating manual is a component of a product.
  • Page 12 SDI 101 S-DIAS SAFETY DIGITAL INPUT MODULE CAUTION Handle the device with care and do not drop or let fall. Prevent foreign bodies and fluids from entering the device. The device must not be opened! Manipulez l’appareil avec précaution et ne le laissez pas tomber.
  • Page 13: Designated Use

    The Safety functions implemented in the product are designed for use with safety applications in a SIGMATEK control and meet the required conditions for safe operation according to SIL 3, HFT 1 n compliance with EN 62061 and according to PL e, Kat. 4 in compliance with EN ISO 13849-1.
  • Page 14: Software/Training

    SDI 101 S-DIAS SAFETY DIGITAL INPUT MODULE Une installation CEM correcte est également incluse dans l’utilisation prévue. Non-designated use consists of: • any changes made to the module or the use of damaged modules. • use of the module inconsistent with the technical margins described in this operating manual or the specifications defined in the technical data.
  • Page 15: Standards And Directives

    S-DIAS SAFETY DIGITAL INPUT MODULE SDI 101 Standards and Directives Residual Risks CAUTION The following residual risks for the product must be included in the system integrator's risk assessment: • Release of non-environmentally safe substances, emissions and unusual temperatures •...
  • Page 16: Functional Safety Standards

    EN ISO 13849-2 - Safety of machinery — Safety-related parts of control systems — Part 2: Validation 3.3.2 EU Conformity Declaration EU Declaration of Conformity The product SDI 101 conforms to the following European directives: • 2006/42/EG Machine Directive • 2014/30/EU Electromagnetic Compatibility (EMC Directive) •...
  • Page 17: Safety-Relevant Parameters

    S-DIAS SAFETY DIGITAL INPUT MODULE SDI 101 Safety-Relevant Parameters 3.4.1 Mounting Position Horizontal 0-55 °C Ambient Temperature Input Module Safety Parameters Safety Level SDI 101 including CPU Single channel use: module SCP 011/SCP = 1.7E-09 (1/h) PL d /Cat. 2 MTTF = 1843 years...
  • Page 18 SDI 101 S-DIAS SAFETY DIGITAL INPUT MODULE Input Module Safety Parameters Safety Level SDI 101 including CPU Single channel use: module SCP 211/SCP = 2.3E-09 (1/h) PL d /Cat. 2 111-S MTTF = 1162 years SIL 3 DC = 97 %...
  • Page 19: Compatibility

    S-DIAS SAFETY DIGITAL INPUT MODULE SDI 101 Compatibility INFORMATION Compatibility For compatibility of the S-DIAS Safety modules, see section "Compatibility of S-DIAS Safety Modules" in the system handbook. Test Signals for Cross-Circuit Detection The module sends pulses in cyclic time intervals to detect a crossed circuit in the outputs.
  • Page 20: Type Plate

    SDI 101 S-DIAS SAFETY DIGITAL INPUT MODULE Type Plate HW: Hardware version SW: Software version Page 18 05.12.2023...
  • Page 21: Technical Data

    S-DIAS SAFETY DIGITAL INPUT MODULE SDI 101 Technical Data Input Specifications The inputs are Type 1 in accordance with EN 61131-2 Number Input voltage +24 V DC Input voltage range minimum +18 V maximum +30 V low: ≤ +5 V high: ≥...
  • Page 22: Signal Output Specifications For Cross-Circuit Detection

    SDI 101 S-DIAS SAFETY DIGITAL INPUT MODULE Signal Output Specifications for Cross-Circuit Detection Number 5x signal A 5x signal B Rated output voltage +24 V DC Output voltage range minimum +18 V maximum +30 V Output current 100 mA at +24 V...
  • Page 23 S-DIAS SAFETY DIGITAL INPUT MODULE SDI 101 05.12.2023 Page 21...
  • Page 24: Input Circuit

    SDI 101 S-DIAS SAFETY DIGITAL INPUT MODULE Input Circuit Miscellaneous Article number 20-891-101 20-891-101-X (polymer coated printed circuit board) Standard UL 508 (E247993) Approbations , CE, TÜV Austria EG type-tested Mission time 20 years Page 22 05.12.2023...
  • Page 25: Environmental Conditions

    S-DIAS SAFETY DIGITAL INPUT MODULE SDI 101 Environmental Conditions Storage temperature -20 ... +85 °C 0 … +55 °C (UL) Environmental temperature 0 … +60 °C (CE) Humidity 0-95 %, non-condensing Installation altitude above sea 0-2000 m without derating level >...
  • Page 26: Mechanical Dimensions

    SDI 101 S-DIAS SAFETY DIGITAL INPUT MODULE Mechanical Dimensions Page 24 05.12.2023...
  • Page 27: Connector Layout

    S-DIAS SAFETY DIGITAL INPUT MODULE SDI 101 Connector Layout 05.12.2023 Page 25...
  • Page 28: Status Leds

    SDI 101 S-DIAS SAFETY DIGITAL INPUT MODULE Status LEDs Bus Status green bus communication OK no supply available BLINKING (5 Hz) no communication Safety-Used yellow module is used and no error module is not used or not in operational mode...
  • Page 29: Label Field

    S-DIAS SAFETY DIGITAL INPUT MODULE SDI 101 Label Field Manufacturer Weidmüller Type MF 10/5 CABUR MC NE WS Weidmüller article number 1854510000 Compatible printer Weidmüller Type Printjet Advanced 230V Weidmüller article number 1324380000 05.12.2023 Page 27...
  • Page 30: Wiring

    SDI 101 S-DIAS SAFETY DIGITAL INPUT MODULE Wiring Wiring Example Page 28 05.12.2023...
  • Page 31: Note

    S-DIAS SAFETY DIGITAL INPUT MODULE SDI 101 Note The input filters, which suppress noise signals, allow operation in harsh environmental conditions. A careful wiring method is also recommended to ensure error-free function. The following installation guidelines should be observed: •...
  • Page 32: Assembly/Installation

    SDI 101 S-DIAS SAFETY DIGITAL INPUT MODULE Assembly/Installation Check Contents of Delivery Ensure that the contents of the delivery are complete and intact. See chapter Contents of Delivery. INFORMATION On receipt and before initial use, check the device for damage. If the device is damaged, contact our customer service and do not install the device in your system.
  • Page 33: Mounting

    S-DIAS SAFETY DIGITAL INPUT MODULE SDI 101 Mounting The S-DIAS modules are designed for installation into the control cabinet. To mount the modules a DIN-rail is required. The DIN rail must establish a conductive connection with the back wall of the control cabinet. The individual S-DIAS modules are mounted on the DIN rail as a block and secured with latches.
  • Page 34 SDI 101 S-DIAS SAFETY DIGITAL INPUT MODULE Recommended minimum distances of the S-DIAS modules to the surrounding components or control cabinet wall: a, b, c … distances in mm (inches) Page 32 05.12.2023...
  • Page 35: 10 Transport/Storage

    S-DIAS SAFETY DIGITAL INPUT MODULE SDI 101 10 Transport/Storage INFORMATION This device contains sensitive electronics. During transport and storage, high mechanical stress must therefore be avoided. For storage and transport, the same values for humidity and vibration as for operation must be maintained! Temperature and humidity fluctuations may occur during transport.
  • Page 36 SDI 101 S-DIAS SAFETY DIGITAL INPUT MODULE 12 Maintenance INFORMATION During maintenance as well as servicing, observe the safety instructions from chapter 2 Basic Safety Directives. 12.1 Service This product was constructed for low-maintenance operation. 12.2 Repair INFORMATION In the event of a defect/repair, send the device with a detailed error description to the address listed at the beginning of this document.
  • Page 37 S-DIAS SAFETY DIGITAL INPUT MODULE SDI 101 Documentation Changes Change date Affected Chapter Note page(s) 11.02.2014 5 Connector Layout Changed image 5.2 Applicable Connectors Connection capacity added French notes added 03.03.2014 5 Connector Layout Changed image 5.1 Status LEDs Changed/expanded Status LEDs table 01.04.2014...
  • Page 38 SDI 101 S-DIAS SAFETY DIGITAL INPUT MODULE 02.04.2019 2.3 Safety-Relevant Correction of the safety-relevant parameters Parameters 3.6 Environmental Conditions Corrections environmental conditions Corrections due to CE 20.09.2019 2.3 Safety-Relevant Values adjusted Parameters 14.11.2019 8 Supported Cycle Times Chapter added 02.12.2019 2.3 Safety-Relevant...
  • Page 39 S-DIAS SAFETY DIGITAL INPUT MODULE SDI 101 05.12.2023 Page 37...

Table of Contents