Installation; Masonry Thick Wall Construction Sleeve Installation - ICE AIR RSNU Installation Manual

Packaged terminal air conditioner (ptac) unit for new construction
Table of Contents

Advertisement

Installation

Masonry Thick Wall
Construction Sleeve Installation
Typical installation for masonry walls is
shown in drawing below.
IMPORTANT: Depending on the size and
style of the louver chosen, you should
determine whether it can be installed before
or after the sleeve installation.
1. Clean the opening of all debris that may
interfere with installation.
2. Be sure the unit's center of gravity falls
within the load bearing surface of the
wall. If the center of gravity is not within
the load bearing surface, then additional
support such as wood, metal or concrete
must be provided in the field.
3. Place a thin pad of soft mortar on the
bottom of the opening.
IMPORTANT: Make certain the wall
sleeve protrudes into the room a
minimum of 1 1/8" beyond the finished
wall surface to accommodate the heat
section and room cabinet. Be sure
to recess the wall sleeve enough to
accommodate outside louver. This
recess is required for stamped louvers
and for architectural louvers. The louver
should be flush to exterior surface when
completed.
4. If a brickstop is employed, slide the
wall sleeve into the wall until the
brickstop contacts the exterior bricks.
If a brickstop is not used, slide wall
sleeve into the wall so it extends into the
room a minimum of 1 1/8" beyond the
finished interior wall surface. The wall
sleeve should also be recessed enough
to accommodate the outside louver.
5. After mortar has dried, remove the
Due to Ice Air's ongoing product development programs, the information in this document is subject to change without notice.
SLEEVE
HEIGHT*
(16-1/4" STD.)
SLEEVE DEPTH
AS REQ'D.*
(12 1/2" MINIMUM)
MIN MASONRY
OPENING*
(16-3/4" STD)
(V.I.F.)
1/4" PITCH
"A"
BOTTOM OF
WALL SLEEVE
OPENING TO F.F.
Notes
1. Wall Sleeve Dimension: (RSNU shown) = 42"w x 16-1/4"h, minimum Wall Sleeve depth: 12-1/4"
2. Enclosure Dimension: Typical 10"d x 22"h x 54"w
3. Kick Plate = B. Varies ("A" - 2 1/2") with ±1" adjustment.
4. 3" above top of Wall Sleeve on roomside must be kept clear for mounting of heating coil and Enclosure.
5. When "A," bottom of Wall Sleeve to finished floor, measures between 2-3/4" to 4-1/2", this necessitates ordering
a front intake Enclosure and Chassis as opposed to a bottom intake.
6. Dimensions "A" and "C," provided for each floor, determine Enclosure height.
* Architect to provide details for each floor.
masonry support from wall sleeve.
NOTE: The wall sleeve is NOT intended
to replace the lintel.
6. Level wall sleeve in all directions and
anchor with appropriate fasteners. It may
be necessary to drill additional holes in
the wall sleeve to firmly secure the unit.
DO NOT drill holes in base of the wall
sleeve. Use shims between the wall and
the wall sleeve to prevent wall sleeve
distortion during anchoring.
7. Caulk wall sleeve (from inside the
7
10-3/4"
MINIMUM
HEATING
3"
COIL
REQUIRED
ENCL.
HEIGHT*
(22" STD.)
KICK PLATE
FINISH
(OPTIONAL)
FLOOR
building) to wall opening on both inside
and outside perimeter using resilient,
non-hardening caulk such as silicone.
DO NOT plug the weep holes.
"C"*
KICK PLATE "B"
("A" - 2-1/2")
HEIGHT
TOP OF
SLAB