FAAST FLEX Product Guide
Piping Design "U" pipe - Dual Channel (FLX-020):
FLX-020 U-pipe network, Class C with In-line filter
Example:
Without Exhaust pipe (E), T-junction 1m (T), Branch of 40m (B1), First hole at 20m (F), 6 holes
1. Verification of project constraints and determination of aspirator speed
N
Number of holes
E
Exhaust pipe
T
T-junction position
B1
Branch length
F
First hole Branch 1 with low speed
with high aspirator speed
PL
Pipe length with
high aspirator speed
L1
Last hole position, Branch 1
2. Calculate nominal step between holes and hole position deviation form nominal
S1 = L1 / ( Number of holes – 1 ) = 20 / 5 = 4 m (≥2.5m)
± 0.2*4m = ±0.8m
3. Determination of necessary Sensitivity Level
and the hole diameters
4
4
4
61
Required
Rules
6
See Table
0m
See Table row C
1m
See Table row A
10m
20m
1.25 ÷ 18m (19-1)
1.25 ÷ 29m (30-1)
40+1+0=41m
≤ 65 m
41-1-20=20m
Number of Branch Holes
Aspirator speed, max 65m for H and 45m for L
A
- Maximum T-Junc on Distance (meters)
l
3
B
- Maximum First Hole Distance (meters)
C
- Maximum Exhaust Pipe Length (meters)
Alarm Level Class C with/without filter
Alarm Level Class B with/without filter
Alarm Level Class A without filter only
1
2
3
4
H/L
H/L
H/L
H/L
H/L
15/15
15/15
15/15
15/15
15/15
30/30
30/30
30/30
30/27
30/23
14/14
14/14
14/14
14/14
14/14
Low
Medium Medium
High
High
High
High
High
High
High
-
-
-
FAAST FLEX
1
5
6
H/L
2
15/15
30/19
3
14/14
High
-
-
4
4
4
-
-
www.xtralis.com