FAAST FLEX Product Guide
Dual Channel:
Pipe Length with low aspirator speed
with high aspirator speed
Exhaust
First hole position, Chamber 1
Last hole position, Chamber 1
Last hole position, Chamber 2
First hole position, Chamber 2
Step between holes
Hole position deviation from nominal position
45° or 90° Bend corresponds to a straight pipe length of
T junction corresponds to a straight pipe length of 1.2m on the common branch
Clips distance
TT
51
Rules
Figure 9-3: Piping Design Parameters - I Pipe
max 50m
PL
max 80m
E
see table
max (see table
F
min 1m
L1
PL - T - F
L2
L1-10%÷L1
F2
F ± 20%*S2
Lx / (Number of branch holes-1)
S1, S2
Sx ± 20%
0.3m
max 1.5m
max 90s
FAAST FLEX
row B
row
A) -E
www.xtralis.com