FAAST FLEX
Example:
E
Exhaust pipe
T
T-junction position
B1
Branch length
F
First hole, Branch 1
PL
Pipe length with low speed
with high aspirator speed
L1
Last hole position, Branch 1
N
Number of holes
B2
Branch 2 length
L2
Last hole, Branch 2
4. For Branch 2, calculate nominal step between holes and hole position deviation from nominal
S2 = L2 / ( Number of holes – 1 ) = 23 / 5 = 4.6 m (≥2,5m)
± 0.2*4.6m = ±0.9m
5. For Branch 2, first hole position can be 5±0.9m
www.xtralis.com
U-pipe network, Class C with In-line filter
Exhaust pipe of 5m (E), T-junction 10m (T), Branch of 30m (B1), First hole at 5m (F), 6 holes
and Branch 2 of 28m (B2)
Required
5m
10
30m
5m
5+10+30=45m
45-5-10-5=25m
6
28m
28-5=23m
Rules
≤ 14 m
≤ 10 m (15m-E)
1.25 ÷ 25m
≤ 45 m
≤ 65 m
See Table
27 ÷ 30m
FAAST FLEX Product Guide
56