Piping Design "U" Pipe - Single Channel (FLX-010):
U-pipe network, Class C with In-line filter
Example:
Exhaust pipe of 5m (E), T-junction 10m (T), Branch of 30m (B1), First hole at 5m (F), 6 holes ...
1. Verification of project constraints and determination of aspirator speed
E
Exhaust pipe
T
T-junction position
B1
Branch length
F
First hole, Branch 1
PL
Pipe length with low speed
with high aspirator speed
L1
Last hole position, Branch 1
N
Number of holes
2. Calculate nominal step between holes and hole position deviation form nominal
S1 = L1 / ( Number of holes – 1 ) = 25 / 5 = 5 m (≥2.5m)
± 0.2*5m = ±1m
3. Determination of necessary Sensitivity Level
cessar
and the hole diameters
3
55
Required
Rules
5m
≤ 14 m
10
≤ 10 m (15m-E)
30m
1.25 ÷ 25m
5m
5+10+30=45m
≤ 45 m
≤ 65 m
45-5-10-5=25m
6
See Table
Number of Branch Holes
Aspirator speed, max 65m for H and 45m for L
2
Alarm Level Class C with/without filter
Alarm Level Class B with/without filter
Alarm Level Class A without filter only
Drilled hole diameter (mm)
1
1
2
3
H/L
H/L
H/L
Low
Low
Medium
High
High
High
High
High
-
6.5
5.5
4.5
H1
H1
H1
FAAST FLEX
1
4
5
6
H/L
H/L
H/L
Medium Medium
High
2
High
High
High
-
-
-
-
3.5
3.5
3
H1
H1
H1
3
www.xtralis.com