 Outlet Control
Setup items
Outlets -
Group 1
Outlets -
Group 2
 Dry Contact Settings
Setup Item
Dry Contact
1 - Input
Dry Contact
2 - Output
Dry Contact
3 - Output
Dry Contact
4 - Output
Remote Control
DB9 - Manual
Bypass
NOTE:
1
*
For detailed information about Option 1, please contact service personnel.
Selectable Value-
Level 2
Output Reboot
Duration
Load Bank
Runtime Limitation
Output Reboot
Duration
Load Bank
Runtime Limitation
Selectable Value
Option 1*
1
: Disable/ ROO/ RPO/ Remote shutdown/
Forced bypass/ On generator
Option 2: 0-999s (per step: 1 sec)
Option 3: Normal open/ Normal close
Disable/ On bat/ Low bat/ Bat fault/ Bypass/ UPS OK/
Load protected/ Load powered/ General alarm/ Overload
alarm
Disable/ On bat/ Low bat/ Bat fault/ Bypass/ UPS OK/
Load protected/ Load powered/ General alarm/ Overload
alarm
Disable/ On bat/ Low bat/ Bat fault/ Bypass/ UPS OK/
Load protected/ Load powered/ General alarm/ Overload
alarm
Option 1: REPO/ ROO
Option 2:
(For REPO) Normally Open/ Normally Closed
(For ROO) Delay Time 0s ~ 999s (per step: 1s)
Enable/ Disable
Selectable Value-
Level 3
Disable/ 5/ 6/.../ 300
Seconds (per step: 1 sec)
Disable/ 1/ 2/.../ 240 mins
(per step: 1 min)
Disable/ 5/ 6/.../ 300
Seconds (per step: 1 sec)
Disable/ 1/ 2/.../
240 mins (per step: 1 min)
41
Default
Disable
Disable
Disable
Disable
Default Value
ROO/ 10s
On Batt.
Low Batt.
General Alarm
REPO/
NO
Disable