Samson 3730-2 Mounting And Operating Instructions page 69

Electropneumatic positioner
Table of Contents

Advertisement

36*
Reset
[OFF]
RUN
ESC
Position transmitter
37
Yes No
38*
Inductive alarm
[NO]
YES
ESC
39
System deviation e info
–99.9 to 999.9 % ,
Transit time Open info
40
0 to 240 s [0]
41
Transit time Closed info
0 to 240 s [0]
42
Auto-w info
0.0 to 100.0 % of the span
4 to 20 mA
Firmware info
43
Xxxx
44
y info
[0] OP
0 to 100 %
MAX
45
Solenoid valve info
Yes
No
Resets all parameters to default (factory setting).
Note: After setting RUN, the positioner must be re-initialized.
Display only,
indicates whether the position transmitter option is installed.
Indicates whether the inductive limit switch option is installed or
not.
Display only,
indicates the deviation from the set point position.
Display only,
minimum opening time is determined during initialization
Display only,
minimum closing time is determined during initialization
Display only,
indicates the supplied automatic reference variable corre-
sponding 4 to 20 mA.
Display only,
indicates the current firmware version of the positioner.
Display only, blocked prior to initialization.
After initialization: indicates the actuator pressure in %.
0 to 100 % corresponds to the pressure range which adjusts the
travel/angle range from 0 to 100 %.
If the actuator pressure is 0 bar, e.g. due to tight-closing on
bottom or fail-safe action, 0 P appears on the display.
If the actuator pressure is higher than the pressure required for X
= 100 %, e.g. due to tight-closing on top, MAX appears on the
display.
Value is determined during initialization.
Display only,
indicates whether a solenoid valve is installed.
Code list
69
EB 8384-2 EN