Samson 3730-2 Mounting And Operating Instructions page 51

Electropneumatic positioner
Table of Contents

Advertisement

Turn
→ Code 16 ,
Retain default value for pressure limit,
change value only if necessary.
Turn
→ Code 17
Retain default. Proceed as follows only if
known:
Press
,
turn
→ Select K
press
.
Turn
→ Code 18 ,
Retain default T
, change only if known.
V
Turn
→ Code 34 , press
turn
→ Select closing direction.
Default OFF
Default 7
,
P
Default 2
Default CCL
,
CCL = counterclockwise and CL = clockwise.
Direction of rotation which causes the valve
to move to the CLOSED position (view onto
the rotary switch movement while positioner
cover is open).
Press
.
mm
Turn
→ Code 35 , press
turn
→ Enter blocking position, e.g.
5 mm (read off at travel indicator scale of
the blocked valve or measure with a ruler).
Press
.
4
Set switch for fail-safe position AIR TO
OPEN or AIR TO CLOSE as described in
section 5.1 on page 42.
4
Set volume restriction as described in
section 5.2 on page 43.
4
Press INIT key!
The positioner switches to manual
operation!
mm
As initialization has not been carried out
completely, the error code 76 (no emer-
Start-up and settings
Default 0.0
,
The adjusted blocking posi-
tion is indicated
EB 8384-2 EN
51