Remak VCS Installation And Operating Instructions Manual page 54

Table of Contents

Advertisement

HMI@Web
3rd Step: Setting the HMI@Web server for Connection
The HMI@Web web server controller can be configured
from the web interface (the same one which serves for
normal operation of the system). Enter the following IP
address http://192.168.1.199 in the address field in
the web browser and confirm with the "Enter" button.
Note: The HMI@Web configuration for the con-
nection itself is not dependent on the browser used.
Enter log-in data in the fields of the Web Server dialog box
– see the figure:
User name:
Password:
On the HMI@Web control web server, there is an account
for a single user. In the u  LAN Connection menu, you can
change the username and password for accessing the web
server. After successfully logging into the HMI@Web control
web server, a dialog window will appear asking for a password
(PIN) to log in to the controller.
Figure 35 – Web Server dialog box
WEB
Figure 36 – Logging in to the controller
Please enter the password (PIN) "4444" in the dialog box
(pre-set access to HMI@Web control from the factory - for
initial setup).
54
WEB
SBTAdmin!
Figure 37 – The home screen
Attention – it is only valid until changed.
These log-in data correspond to the highest level user authori-
sation (role: service) – they should only be reserved for the
supplier performing the installation or the service provider.
It is advisable to change the log-in data as soon as upon first
log-in (Passwords u Password change – actual or lower ac-
cess level password change is offered). The dialog box to enter
a new password is displayed at the bottom of the browser.
Press the Save button to confirm and save the changes to
the settings.
Warning
Once the changes have been made, it will no longer be possible
to use the original data to log in. Keep your log-in data safely
stored (keep them confidential). If you lose them, contact the
manufacturer or authorized service representative.
Apart from the service log-in data, it is also necessary to
modify other user pre-set log-in data to enable access to the
HMI@Web controller for the operating staff – rename them
according to the actual authorised users and change the
corresponding passwords:
Role
Password
SERVICE
4444
ADMINISTRATOR
3333
USER
2222
GUEST
0000
Note: If the user settings are not performed within this phase
of commissioning, it is necessary to perform them at the lat-
est during training of the operating staff or device handover
to the end user.