List of Data Points (HMI-SG controller)
Parameter
Notation
Reading
code
level
code
level
458
A
459
U
Start-up sequence delay
Gas heating
460
A
461
U
Cooling sequence enabling
462
A
463
U
Minimum burner run time
464
A
465
U
Minimum burner downtime
466
A
467
U
Burner restart protection time (burner Stage 1)
468
A
469
U
Modulation burner opening/closing speed (burner Stage 1)
470
A
471
U
Heating request value for the burner Stage 2 switch-off
472
A
473
U
Maximum flue-gas temperature setting for alarm
474
A
475
U
Maximum flue-gas temperature
476
A
477
U
Requested flue-gas temperature
478
A
479
U
Minimum flue-gas temperature
Electric heating
480
A
481
U
Electric heating switching on – request for heating
482
A
483
U
Electric heating hysteresis
Mixing
484
A
484
A
Minimum fresh air flow rate setting
484
A
484
A
Minimum fresh air flow rate setting - Comfort mode (pool unit)
485
A
485
A
Minimum fresh air flow rate setting - Economy mode (pool unit)
486
A
487
U
Starting temperature for mixing damper wide-open position
488
A
489
U
Starting time for mixing damper wide-open position
490
U
Mixing damper control signal recurrence vale (normal/inverse)
Function of the maximum fresh air limit (ventilation unit)
563
A
564
U
Maximum fresh air limit based on outdoor temperature
565
A
566
U
Outdoor temperature from which the maximum fresh air limitation is activated
567
U
Information about the activation of the
maximum fresh air limitation
Electric pre-heating
491
A
492
U
Required temperature for pre-heating
493
A
494
U
Outdoor dependent electric pre-heating blocking
495
A
496
U
Heating request dependent el. –pre-heating switch-on
497
A
498
U
Hysteresis for electric pre-heater switch-off
Electric reheating
502
A
503
U
Heating request dependent electric re-heating start-up for Stage 1
504
A
505
U
Hysteresis for electric re-heating switch-off
506
A
507
U
Fan stage dependent outlet limitation ST1
508
A
509
U
Fan stage dependent outlet limitation ST2
510
A
511
U
Fan stage dependent outlet limitation ST3
512
A
513
U
Fan stage dependent outlet limitation ST4
514
A
515
U
Fan stage dependent outlet limitation ST5
Heat recovery
516
A
517
U
Freezing determination temperature exchanger
518
A
519
U
Start temperature for maximum - HRE speed/volume open BP PE
520
A
521
U
Start time for maximum - HRE speed/volume open BP PE
522
A
523
U
Heat recovery request dependent HRE run enabling
524
A
525
U
Hysteresis for HRE run stop
526
U
Information - antifreeze protection start-up
Night turning
527
A
528
U
Time to next turning
529
A
530
U
Active turning time
Humidification
531
A
532
U
Desired relative humidity - Comfort
535
A
536
U
Desired relative humidity - Economy
541
A
542
U
Blocking humidification in summer
Menu HMI-SG
Meaning
0
without cooling
1
with cooling
0
inactive
1
active
0
inactive
1
active
0
No
1
Yes
Control units VCS
Factory Settings
Value
120
150
150
150
5
40
230
210 400
210
160 p.472
160
150 210
150
100 160
20
10
20
20
20
15
60
100
40
-10
-100 100
-20
-30
20
10
20
10
100
100
100
100
100
1
15
60
38
5
3
300
40
30
0
Min
Max
10
600
s
0
600
s
0
600
s
0
600
s
0
20
%/s
10
100
%
°C
°C
°C
°C
0
100
%
1
100
%
0
100
%
0
100
%
0
100
%
-64
64
°C
0
600
s
0
100
%
0
100
%
°C
-50
10
°C
-50
10
°C
0
100
%
0
100
%
0
100
%
1
100
%
0
100
%
0
100
%
0
100
%
0
100
%
0
100
%
-64
64
°C
-64
64
°C
0
600
s
0
100
%
0
100
%
0
9999
h
0
9999
s
0
100
%r.H.
0
100
%r.H.
39