List of Data Points (HMI-SG controller)
Parameter
Notation
Reading
code
level
code
level
261
S
Signal inversion for heat pump, cooling
262
S
Switching to special signal 0-10V (Daikin)
263
S
The difference between the demand and the actual signal to determine St2
264
S
Time it takes for the signal to transition from 0 to 100%
265
S
Voltage signal for heating demand (Toshiba)
266
S
Voltage signal for cooling demand (Toshiba)
267
S
Voltage signal for Stop demand (Toshiba)
268
S
Voltage signal for Start demand (Toshiba)
Cooling
393
A
394
U
Outdoor temperature to enable cooling – all versions
395
A
396
U
Minimum pump operating time – water version
397
A
398
U
Pump downtime to the pump turning activation – water version
399
A
401
U
Active pump turning time – water version
397
A
398
U
Minimum operating time, single-stage condensing unit – version with single-stage condensing unit
399
A
401
U
Re-cooling blocking time – versions with single-, two-stage condensing units
402
A
403
U
Retention time during transition from Stage 1 to Stage 2 – version with two-stage condensing unit
404
A
405
U
Cooling request dependent evaporator Stage 1 switch-on – version with two-stage condensing unit
406
A
407
U
Cooling request dependent evaporator Stage 2° switch-on – version with two-stage condensing unit
408
A
409
U
Hysteresis for transition from Stage 1 to Stage 2, two-stage condensing unit
410
A
411
U
Minimum inverter operating time – version with inverter
412
A
413
U
Inverter re-start blocking time – version with
single-stage condensing unit + inverter
413
A
Inversion of the cooling analog output signal
Water heating with pre-heating function
414
A
415
U
Outdoor temperature-dependent pump start-up in the AHU Stop and Run mode
416
A
417
U
Minimum pump run time
418
A
419
U
Pump downtime to the pump turning activation
420
A
421
U
Active pump turning time
422
A
423
U
Active function preheating of water operation time
424
A
425
U
Pre-heating function blocking time between AHU unit shut-down and restart
426
A
427
U
Water heater circuit heating curve setting at the AHU start-up X1
428
A
429
U
Water heater circuit heating curve setting at the AHU start-up Y1
430
A
431
U
Water heater circuit heating curve setting at the AHU start-up X2
432
A
433
U
Water heater circuit heating curve setting at the AHU start-up Y2
434
A
435
U
Stop to Run mode switching delay AP trigger value
436
A
437
U
Water heat exchanger dependent AP trigger value – AHU in Run mode
438
A
439
U
Water heat exchanger dependent AP trigger value - AHU in Stop mode
440
A
441
U
Inlet air dependent AP evaluation enabling delay after the unit start-up
442
A
443
U
Inlet air temperature dependent AP start-up – failure alarm A
444
A
445
U
Inlet air temperature dependent AP start-up
446
A
447
U
Maximum return water temperature
Water pre-heating
448
A
449
U
Outdoor dependent pre-heating (pump) start-up
450
A
451
U
Pump downtime to the pump turning activation
452
A
453
U
Active pump turning time
454
A
455
U
Minimum pump run time
Heating water source switching
456
A
457
U
Limit value for heating
38
Menu HMI-SG
Meaning
1
On
0
Off
1
On
0
Off
1
On
0
Off
1
On
Factory Settings
Value
Min
Max
40
0
100
%
120
0
500
s
3,25
0
10
V
6,25
0
10
V
0
0
10
V
8
0
10
V
12
-64
64
°C
180
0
9999
s
168
0
9999
h
60
0
9999
s
60
0
9999
s
120
5
600
s
360
5
600
s
20
0
100
%
70
0
100
%
10
0
20
%
10
0
9999
s
60
0
300
s
5
-64
64
°C
180
0
9999
s
168
0
9999
h
60
0
9999
s
120
0
600
s
5
0
30
min
-10
-30
5
°C
100
0
100
%
10
0
50
°C
10
0
100
%
60
0
600
s
15
0
50
°C
30
0
50
°C
60
0
600
s
6
-64
64
°C
8
-64
64
°C
70
20
140
°C
5
-50
15
°C
168
0
9999
h
30
0
9999
s
30
0
9999
s
15
5
25
°C