List of Data Points (HMI-SG controller)
Parameter
Notation
Reading
code
level
code
level
272
U
Regulation additional fan
273
U
Heating
274
U
Heat pump
275
U
Type of gas heating
276
U
Byppas damper gas heater
277
U
Cooling
278
U
Heat recovery
279
U
Mixing
280
U
Preheating
281
U
Extra heating
282
U
Temperature control mode
283
U
Humidity control mode
Control parameters
Temperature start-up
301
A
302
U
Cooling trigger temperature
303
A
304
U
Heating trigger temperature
305
A
306
U
Hysteresis
307
A
308
U
Heating and cooling blocking time
309
A
310
U
Operating time
Night colling
311
A
312
U
Temperature hysteresis
313
A
314
U
Minimum outdoor temperature setting
315
A
316
U
Outdoor temperature and room temperature difference
317
A
318
U
Minimum night chilling operating time
Boost function
319
A
320
U
Pre-set interval before time program start-up
321
A
322
U
Temperature hysteresis
Required temperature compensation
36
Menu HMI-SG
Meaning
0
none
1
1 stage
2
5 stage (TRN)
3
V10
4
V100
7
2xV10
8
2xV100
0
no
1
water
2
electric
3
gas
0
no
1
variation A
2
variation B
0
1 stage
1
2 stage
2
modulation
0
no
1
yes
0
no
1
water
2
1 step
3
2 step
4
inverter
5
inverter + 1 step
0
no
1
plate
2
wheel
3
glycol
0
no
1
yes
0
no
1
water
2
electric
0
no
1
electric
0
supply
1
cascade - room
2
cascade - return
0
no
1
room
2
supply
3
cascade - room
Factory Settings
Value
Min
Max
30
-64
64
°C
25
-64
64
°C
1
0,1
64
°C
30
0
999
min
0
0
999
min
3
0
64
°C
12
-64
64
°C
5
1
64
°C
30
0
999
min
60
0
999
min
0,5
-64
64
°C