List of Data Points (HMI-SG controller)
List of Data Points (HMI-SG controller)
Parameter
Notation
Reading
code
level
code
level
545
U
Humidification power
550
G
Calculated current desired humidity value in the cascade
Dehumidification
533
A
534
U
Dehumidification required relative value - Comfort
537
A
538
U
Dehumidification required relative value - Economy
539
A
540
U
Maximum humidity required value
543
U
Current humidity value
544
U
Maximum humidity
546
U
Dehumidification output
547
U
Dew point
548
A
549
U
Dew point deviation
551
G
Calculated current dehumidification required value for cascade control
Humidity-dependent fan speed compensation
554
A
555
U
Fan speed compensation function
556
U
Compensation display
Compensation of the position of the mixing damper based on humidity
560
A
561
U
Function of fan speed compensation
562
U
Display of compensation value
Control constants
Cooling factors (all versions)
601
S
602
A
Proportional factor
603
S
604
A
Integrating factor
605
S
606
A
Derivative factor
Heat pump factors - heating
607
S
608
A
Proportional factor
609
S
610
A
Integrating factor
611
S
612
A
Derivative factor
Heat pump factors - cooling
613
S
614
A
Proportional factor
615
S
616
A
Integrating factor
617
S
618
A
Derivative factor
Room (outlet) temperature dependent fan speed compensation
619
S
620
A
Proportional factor
621
S
622
A
Integrating factor
623
S
624
A
Derivative factor
Heating dependent fan speed compensation
625
S
626
A
Proportional factor
627
S
628
A
Integrating factor
629
S
630
A
Derivative factor
Cooling dependent fan speed compensation
631
S
632
A
Proportional factor
633
S
634
A
Integrating factor
635
S
636
A
Derivative factor
Air quality CO2 (VOC,CO) dependent compensation (damper position/fan speed)
637
S
638
A
Proportional factor
639
S
640
A
Integrating factor
641
S
642
A
Derivative factor
Mixing
643
S
644
A
Proportional factor
645
S
646
A
Integrating factor
647
S
648
A
Derivative factor
Heat recovery RHE/BP PE
649
S
650
A
Proportional factor
651
S
652
A
Integrating factor
653
S
654
A
Derivative factor
Heat recovery – antifreeze protection
40
Menu HMI-SG
Meaning
0
increase
1
decrease
0
increase
1
decrease
Factory Settings
Value
Min
Max
%
60
0
100
%r.H.
70
0
100
%r.H.
80
0
100
%r.H.
%
%
°C
1
-64
64
°C
%r.H.
0
%
0
%
-5
60
s
0
s
5
300
s
0
s
-5
300
s
0
s
20
0
s
0
s
5
120
s
0
s
-10
120
s
0
s
-0,3
300
s
0
s
7
45
s
15
s
3
60
s
1
s