List of Data Points (HMI-SG controller)
Parameter
Notation
Reading
code
level
code
level
750
S
751
A
Integrating factor
752
S
753
A
Derivative factor
Constant flow (pressure) regulation - supply
754
S
755
A
Proportional factor
756
S
757
A
Integrating factor
758
S
759
A
Derivative factor
Constant flow (pressure) regulation - exhaust
760
S
761
A
Proportional factor
762
S
763
A
Integrating factor
764
S
765
A
Derivative factor
Humidity-based mixing damper position compensation
766
S
767
A
Proportional factor
768
S
769
A
Integrating factor
770
S
771
A
Derivative factor
Checks, system and network settings
Difference between required and inlet temperature monitoring
801
A
802
G
Maximum difference (±°C)
803
A
804
G
Minimum limit (°C)
805
A
806
G
Time delay after AHU start-up (s)
Difference between required and room (outlet) temperature monitoring
807
A
808
G
Maximum difference (±°C)
809
A
810
G
Minimum limit (°C)
811
A
812
G
Time delay after AHU start-up (s)
Remote fault
813
A
814
G
Failure class selection to digital output
815
G
Alarm message (generated depending on priorities)
Fire mode
816
A
817
G
Fan behaviour during fire selection
818
A
819
G
Fan output during fire selection
820
A
821
G
Fire alarm activation inlet temperature
822
A
823
G
Fire alarm activation outlet temperature
Alarm number for HMI
824
U
Alarm number
System settings - control unit
825
A
825
A
Failure acknowledgement (reset of all fail-
ures after they have been removed)
826
S
826
S
Software reset of the controller
827
S
827
S
Control unit location building physical address
828
S
828
S
Control unit location floor physical address
829
S
829
S
Control unit device address
SD card
830
S
Loading an application from an SD card
834
S
Parameter save SD card
835
S
Parameter save SD card - successful
836
S
Parameter load SD card
837
S
Parameter load SD card - successful
42
Menu HMI-SG
Meaning
0
Failure A
1
Failure A+B
0
Normal
1
Alarm
0
Stop
1
Inlet fan
2
Outlet fan
3
Both fans
0
No
1
Yes
0
without reset
1
reset
0
No change
1
Loading
0
Passive
1
Active
0
No
1
Yes
0
Passive
1
Partial
2
Full
0
No
Factory Settings
Value
Min
Max
45
s
0
s
0,3
30
s
0
s
0,3
30
s
0
s
-2
45
s
0
s
10
0
99
°C
10
0
99
°C
60
0
9999
s
10
0
99
°C
10
0
99
°C
600
0
9999
s
1
0
80
0
100
%
70
0
99
°C
50
0
99
°C
0
0
15
0
0
15
0
0
250