List of Data Points (HMI-SG controller)
Parameter
Notation
Reading
code
level
code
level
058
G
Calculated absolute inlet air humidity
059
G
Calculated inlet air humidity enthalpy
060
G
Calculated absolute room air humidity
061
G
Calculated room air humidity enthalpy
062
G
Calculated absolute outdoor air humidity
063
G
Calculated outdoor air humidity enthalpy
064
G
Request for dehumidification
065
G
Request for humidification
066
G
Humidifier status
Settings
Temperature modes
101
A
102
G
Comfort - cooling
103
A
104
G
Comfort - heating
105
A
106
G
Economy - cooling
107
A
108
G
Economy - heating
109
A
110
G
Required temperature for cooling, Temperature start-up
111
A
112
G
Required temperature for heating, Temperature start-up
113
A
114
G
Required room temperature , Night chilling (control for inlet)
115
A
116
G
Required room temperature , Boost (control for inlet)
117
A
118
G
Required temperature for cooling, Boost
119
A
120
G
Required temperature for heating, Boost
Cascade control limitation - limiter
121
S
122
A
Max. difference between room temperature and inlet temperature
123
S
124
A
Min. difference between room temperature and inlet temperature
Operation mode
125
A
126
G
AHU manual control (Tempera-
ture mode, fan output stage)
127
A
128
G
AHU start-up time-out after power supply failure
External control
129
U
130
G
External contact function defini-
tion (Ext. control 1 contact)
131
U
132
G
Transition time from ext. control mode to
AUTO mode (Ext. control 1 contact)
133
U
134
G
Fan output stage setting
(Ext. control 1 contact or 2 contacts)
135
U
136
G
Temperature mode setting
(Ext. control 1 contact or 2 contacts)
137
U
138
G
Fan output stage setting "Higher"
(Ext. control 2 contacts)
Menu HMI-SG
Meaning
0
off
1
on
0
Auto
1
Stop
2
Economy; St1
3
Comfort; St1
4
Economy; St2
5
Comfort; St2
6
Economy; St3
7
Comfort; St3
8
Economy; St4
9
Comfort; St4
10 Economy; St5
11 Comfort; St5
0
Start function
1
Start and Stop function
0
Auto
1
off
2
Stage 1
3
Stage 2
4
Stage 3
5
Stage 4
6
Stage 5
0
Comfort
1
Economy
0
Auto
1
off
2
Stage 1
3
Stage 2
Control units VCS
Factory Settings
Value
24,6
22,6
28
20,6
15
25
22
20
15
25
10
10
Stop
10
0
0
2
0
5
Min
Max
g/kg
kJ/kg
g/kg
kJ/kg
g/kg
kJ/kg
%
%
0
99
°C
0
99
°C
0
99
°C
0
99
°C
-64
64
°C
-64
64
°C
-64
64
°C
-64
64
°C
-64
64
°C
-64
64
°C
0
64
°C
0
64
°C
0
9999
s
0
23
h
31