Echoflex Installation Guide
Ceiling & High Bay Occupancy Sensor
When the space is vacant and the controller is configured for
occupancy, a PIR detection or manual control can change the state
to occupied.
When the space is vacant and the controller is configured for
vacancy, only manual control can change the state to occupied.
A vacancy message is sent after 200 seconds of inactivity, and then
subsequent messages every 1000 seconds.
Dual Technology (DT Models)
When both PIR and audio sensing are enabled, the following logic is used:
When the space is occupied, PIR and audio detection can reset both
the sensor's Occupancy Timer and the controller's Occupancy Timer.
When the space is vacant and all timers have expired, only PIR
detection or manual control can change the state to occupied, if the
sensor is configured for occupancy.
When audio is detected in an occupied space, the sensor's
Occupancy Timer is reset, but not the Audio Enabled Timer; it expires
after 60 minutes or is reset by PIR detection.
A vacancy message is sent after 20 minutes (default) of no detection,
then 40 seconds later the audio is disabled. The 40-second grace
timer allows an occupant sufficient time to use sound to reset the
sensor's Occupancy Timer.

Lens Masking

Lens mask stickers are provided to
block a section of the lens from
detecting occupancy. To attach,
remove the backing and stick the mask
on the sensor lens to cover the target
section. Cut to size, if required.
Link to a Controller
The compatible target controller must
be installed, powered, and within
range of the MOS.
Note:
controller and to unlink a linked device from a controller.
1. Press the [Learn] button on the controller to activate Link mode. If
necessary, refer to the controller product documentation.
2. Press the [Teach] button on the front of the sensor once to send a
message.
3. Deactivate Link mode on the controller before attempting to link to
any other controllers.
Ceiling & High Bay Occupancy Sensor
The linking process can be used both to link a device to a
Page 4 of 12