Lens Masking - ETC Echo Dual Tech Installation Manual

Ceiling-mount vacancy sensor
Hide thumbs Also See for Echo Dual Tech:
Table of Contents

Advertisement

ETC Installation Guide
Dual Tech Vacancy Sensor
Walk Test
The sensor offers a Walk Test mode, which shortens the vacancy timer to
10 seconds and allows for simple and quick verification of the sensor's
coverage and range in the installed space.
1. Prepare the site for configuration.
a. Make certain the sensor and lighting loads are powered and
connected for control by the Echo control system.
b. You will need direct access to the sensor in order to place it into
Walk Test mode.
2. Press the [Walk Test] button on the sensor to enable the Walk Test
feature. A green LED flashes, indicating Walk Test is enabled and
the vacancy timer is shortened to 10 seconds.
3. Move throughout the space, including corners and areas that may
be obscured from line of sight to the sensor. Each time the sensor
detects movement, the lens illuminates red. If acoustic detection is
enabled, any sound detected illuminates the lens green.
4. Adjust the lens masking, if installed, blocking certain areas of the
installed space from sensor detection. See
5. Walk Test mode automatically exits and the sensor returns to
normal operation after five minutes. You can also manually
terminate by pressing the [Walk Test] button again.

Lens Masking

Lens masks are provided in the packaging for your convenience. Use this
to block a section of the lens from detecting occupancy. To attach, cut to
the desired size, remove the backing and stick it on the sensor lens,
covering the desired sections.