Sensor Setting - ETC echoflex MOS-IR A Series Installation Manual

Ceiling & high bay occupancy sensor
Hide thumbs Also See for echoflex MOS-IR A Series:
Table of Contents

Advertisement

Echoflex Installation Guide
Ceiling & High Bay Occupancy Sensor
The test repeats every five seconds and runs for 50 seconds. To exit
before the time-out, press and hold the [Teach] button.
Walk Test
The Walk Test verifies the boundaries or limits of the sensor's range.
1. Press and hold the [Teach] button until the green LED is displayed.
Release the button to enter the menu and display the first item, the
blinking green LED.
2. Press and release the [Teach] button to cycle through the menu of
color LEDs and stop when the red LED is blinking.
3. Press and hold the [Teach] button until the LED stops blinking to
initiate the Walk Test.
4. Move throughout the space including corners and areas that may be
obscured from line of sight to the sensor. Each time the sensor
detects movement, the red LED blinks. If audio sensing is enabled
(DT model), the green LED blinks when sound is detected.
5. Adjust the lens masking, if required, to block certain areas of the
space from sensor detection. See
The Walk Test times out after 100 seconds of inactivity. To exit before the
time-out, press and hold the [Teach] button for 10 seconds.

Sensor Setting

The Sensor Setting adjusts PIR Sensitivity, Audio Sensitivity, and Sensor
Occupancy Timer duration. To reduce false occupancy states caused by
external elements, consider adjusting the sensitivity setting.
1. Press and hold the [Teach] button until the green LED is displayed.
Release the button to enter the menu and display the first item, the
blinking green LED.
2. Press and release the [Teach] button to cycle through the menu of
color LEDs and stop when the red and blue LEDs are both blinking.
3. Press and hold the [Teach] button until the LEDs stop blinking to
select Sensor Setting.
4. Press the [Teach] button to cycle through the options:
Two green blinks - PIR Sensitivity
Two blue blinks - Audio Sensitivity (DT model only)
Two red blinks - Occupancy Timer (DT model only)
Note:
Echoflex Dual Tech sensors have a configurable Occupancy
Timer that sends a vacancy message when expired. If using another
brand of controller with a DT model, you may want to adjust the
Occupancy Timer on the sensor to control vacancy messaging.
5. Press and hold the [Teach] button again to select an option. The
corresponding LED blinks according to the current setting.
Ceiling & High Bay Occupancy Sensor
Lens Masking on
Page 7 of 12
page 4.