RSMZ Module VFD Status Trend Log Table 17: ........................53 VCCX2 Trend Log Bit Strings Table 18: ..........................55 VCCX2 Trend Log Bit Strings (continued) Table 19: ......................56 0-5V Temperature Sensor - Voltage and Resistance for Type III Sensors Table 20: .............59...
It also has an on-board BACnet port for connection • Indoor air quality economizer reset to an MS/TP network. The VCCX2 contains a 2 x 8 LCD character display and four buttons that allow for status and alarm display, •...
Application assumes unit has return air to allow for unoccupied operations with outdoor air damper closed. Dehumidification mode utilizes the outdoor air dewpoint and resets the coil temperature based off the supply air dewpoint. VCCX2 Controller Technical Guide...
OR THE CONTROLLER CONNECT G040660 CONNECT WILL BE DAMAGED 1002 OPTIONS 1002 0.20 ADDRESS .01uF 0.62 2.05 4.10 Note: All Dimensions are in inches. Note: Depth is 1.50 inches. Figure 3: VCC-X EM1 Expansion Module Dimensions VCCX2 Controller Technical Guide...
• When communication wiring is to be used to connect The VCCX2 Controller is housed in a plastic enclosure. It is VCCX2 Controllers together or to connect to other designed to be mounted by using the three mounting holes in the communication devices, all wiring must be plenum-rated, enclosure base.
Connect FRP Tubing to High Pressure Port (bottom tube) and route to Static Pressure Pickup Probe located in unit discharge. Plug into VCCX2 Leave port marked “LO” open to atmosphere. Controller’s Duct Static Port Figure 5: VCCX2 Controller Input Wiring VCCX2 Controller Technical Guide...
WIRING VCCX2 Controller Outputs NOTE: All Relay Outputs are normally open and rated for 24 VAC power only. 1 amp maximum load Waterside Economizer V alve Figure 6: VCCX2 Controller Output Wiring VCCX2 Controller Technical Guide...
WIRING VCC-X EM1 Expansion Module The VCC-X EM1 Expansion Module connects to the VCCX2 It is very important to be certain that all wiring Controller with an E-BUS cable and adds an additional five analog WARNING: is correct as shown in the wiring diagram inputs, five analog outputs, three binary inputs, and five configurable below.
24 VAC POWER ONLY WARNING! POLARITY MUST BE OBSERVED E-BUS LABEL P/N: E-BUS OR THE CONTROLLER CONNECT G040660 CONNECT WILL BE DAMAGED (for Return Plenum Pressure Control Applications) Figure 10: VCC-X EM1 Expansion Module Output Wiring VCCX2 Controller Technical Guide...
WIRING Airflow Station The E-BUS Adapter Board attaches to the VCCX2 Controller with The Airflow Station’s baud rate needs to be set to 19,200 in order an E-BUS cable. The Adapter Board is used for connecting the to communicate with the VCCX2 Controller (excludes Paragon EBTRON, GreenTrol, or Paragon Airflow Measurement Digital MTSE).
VCCX2 sizing for each controller. Each VCCX2 Controller requires 15 VA Controller in the order that follows: of power delivered to it at 24 VAC. Use separate transformers for each device (preferred) or power several devices from a common Configure the controller for the application.
Table 5: VCCX2 Controller Relay Outputs Dirty Filter The following E-BUS sensors and modules are available to connect Hood On/Off to the VCCX2 Controller via E-BUS ports or E-BUS Expansion Remote Forced Occupied Modules: Remote Forced Cooling • E-BUS Digital Room Sensor - LCD Display - Temp Only...
INPUTS AND OUTPUTS VCCX2 Controller and EM1 Module Inputs/Outputs Maps EM1 Expansion Module Inputs ANALOG INPUTS (AI) INPUT NAME Entering Water Temperature Sensor Mixed Air Temperature sensor SIG1 Return Air Plenum Pressure (0-5V) SIG2 Economizer Damper Midway Switch (5VDC) SIG3...
BI3 - Hood On/Off Input This sensor is only required if configuring the VCCX2 Controller When this wet contact input closes (hood on), the VCCX2 Controller for building pressure control. Building pressure control can be switches from indoor air control to outdoor air control. This is accomplished by using one of two main control methods.
Page 27
The controller remains active and can initiate alarm relays. For reverse acting building pressure control using the NOTE: outdoor air damper or supply fan VFD, the VCCX2 The binary inputs require wet contacts (24 VAC only) NOTE: Controller uses the outputs specific to those devices.
This static pressure reading is used to control the output These relays are configurable by the user. See Table 10, page 29 signal (AO4 on the VCCX2 Controller) supplied to the exhaust fan VFD. Binary Inputs BI1 - Return/Exhaust Proof of Flow...
If configured, this relay will energize anytime the space sensor push-button override is active. Alarm Active If configured, this relay will energize anytime a VCCX2 alarm is active. A1 Comp Run Status Will enable when the RSM A1 compressor activates.
Space Temperature Typical selection for CAV recirculating units. • Broadcast week schedule from GPC-XP The VCCX2 Controller can be forced into the Occupied Mode by Return Air Temperature Optional selection for CAV recirculating units. inputting a forced schedule from any operator interface.
Page 31
When the remote forced occupied signal is removed, the controller will revert to the Unoccupied Mode of operation, or if an internal VCCX2 schedule is also being used, it will revert to the current scheduled mode. Setting the internal week schedule to “0” will cause the controller to only look for the remote forced occupied signal for occupied/ unoccupied commands.
Cooling with the Refrigerant System Modules the active Supply Air Cooling Setpoint. The modulating cooling On units with digital or VFD compressors, the VCCX2 Controller proportional window is used to determine the signal to the chilled will utilize one or more RSMs. Units with only fixed staged water valve and is user adjustable.
Page 33
VCCX2 controller is wired to the direct fire controller to adjust (adjustable) before it is allowed to energize, and successive stages the amount of heat it puts out. The VCCX2 uses the same modulating are subject to a heating stage up delay (adjustable).
Page 34
Damage to the unit could occur since the outdoor air damper remains default of 0%, the controller will not initiate this protection sequence. closed in the Unoccupied Mode. This operation works during emergency shutdown. VCCX2 Controller Technical Guide...
Page 35
Dehumidification Operation on Chilled Water Units If the unit is equipped with a MHGRV-X, during Dehumidification it For chilled water units, the VCCX2 Controller will open the chilled will modulate the reheat valve to maintain the supply air temperature water valve to a fixed 100% position to provide full moisture at the active Supply Air Temperature Setpoint.
Page 36
Heat Pump Standard Defrost Operation If using the VCCX2 Controller with an installed defrost coil When the SAT rises above the SAT setpoint the MHGRV will temperature switch, a defrost cycle is available.
Page 37
SEQUENCE OF OPERATIONS Modes of Operation Heat Pump Adaptive Defrost Operation When the VCCX2 Controller is configured for Morning Warm-Up The adaptive defrost operation adjusts the time interval (adaptive and switches to the Occupied Mode of Operation (not Override or defrost timer) in between Defrost Mode cycles.
Page 38
If utilizing the Title 24 economizer option, an economizer feedback signal (0-10 VDC) can be wired into the VCC-X EM1 Expansion Module for status monitoring. Several Title 24 alarm conditions can also be displayed. VCCX2 Controller Technical Guide...
Page 39
The digital sensors each need to be configured with unique addresses (#1 -10) and have an LCD display for this operation. In A remote contact control option can be configured on the VCCX2 this arrangement, only the sensor at address #1 can utilize the slide Controller to initiate the HVAC Modes of operation.
Page 40
Outdoor Air Temperature Sensor connected directly to the established by the configured Low and High Supply Air Temperature VCCX2 Controller) will be used as the temperature that locks out Setpoints. compressors during heat pump heating mode. See the PREHEAT-X Module Technical Guide for more details.
Page 41
In order to maintain a constant cubic feet per minute through the unless close observation reveals that the supply fan or bypass damper supply air ducts on a mixed air constant air unit, the VCCX2 can is hunting and not maintaining a stable pressure reading.
Page 42
This is done to prevent any damage to either the return or Outdoor Air Damper exhaust damper assemblies. If this option is configured, the VCCX2 will use the user-adjustable economizer/outdoor air damper output signal (AO2 – Economizer Control Signal) to maintain the Building Pressure Setpoint.
Page 43
The air being exhausted is controlled by a separate control system hours. This is accomplished by simply configuring Night Setback that sends the VCCX2 a 0-10 VDC signal on analog input 6 based Temperature Setpoints (anything other than the default 30ºF) on a on its exhaust demand.
Page 44
Space Heating High and a Space Heating Low If there is no demand, the VCCX2 switches to Vent Mode. If the Reset Source Setpoint. outdoor air temperature is greater than the Hood On HVAC Cooling...
Page 45
In this operation, if night setback operation will be initiated by the Sump Heater Enable Temperature Setpoint. The sump heater a Space Sensor connected to the VCCX2 Controller, then the relay deactivates once the sump temperature rises 10ºF above the...
Page 46
The sump and condenser valves are open. drain enable relay can be disabled in one of two ways: 1. Cycle power to the VCCX2 when the sump temp is above For waterside economizer bypass wiring, please see NOTE: the Sump Drain Enable Setpoint or the RSMD Technical Guide.
CO control. Relief Pressure Sensor This alarm occurs if the VCCX2 is receiving the value from a Broadcast or BACnet and the value is out of an acceptable range. Airflow Alarms •...
Page 48
A 24 VAC wet contact input is available to be used when a normally closed smoke Detector, Firestat, or other shutdown condition occurs. If this contact opens, it will initiate shutdown of the VCCX2 and will generate an alarm condition. If an Occupied relay is configured, it will remain energized.
Expansion Boards If the controller is configured to have any of the below expansion boards (Modules), but the VCCX2 controller does not detect that board, then the applicable alarm will occur. If the board is properly detected after the unit has alarmed, the alarm will be cleared.
In the Prism 2 Alarm Menu, Click OK on Compressor Alarms and the following detail screen will appear: Refer to the individual RSM Technical Guides for more details. Figure 18: Prism 2 EVAP Module Alarms Screen Figure 17: Prism 2 Compressor Alarms Screen VCCX2 Controller Technical Guide...
AlrmGrp5 (Bit String)* Refrigeration Module Alarms Table 12: RSMZ Module Trend Log Binary Inputs Status Bin IN (Bit String)* Relays Status of VCCX2 and EM1 Main Rly (Bit String)* Relays Status of 12 Relay Expansion Exp Rly (Bit String)* Module * Bit String and Enumeration Value information and interpretation is explained in the paragraphs and tables at the end of this section.
A2 Discharge Temperature 1DisChg2 (ºF) Relay Status 1Relay1 (Bit String)* * Bit String and Enumerated Value information and interpretation is explained in the paragraphs and tables at the end of this section. Table 13: RSMV/RSMD Module Trend Logs VCCX2 Controller Technical Guide...
Page 54
The tables on the following pages provide the bits, values and to decode the VCCX2 trend log items that are indicated as being descriptions for the various points on the VCCX2 Controller and bit string values.
Defrost Mode Relay 1 Active Relay 2 Active RSMV/RSMD 1Relay1 Relay 3 Active 2Relay2 Relay 4 Active 3Relay3 Relay 5 Active 4Relay4 Unloader 1 Active Unloader 2 Active Table 19: VCCX2 Trend Log Bit Strings (continued) VCCX2 Controller Technical Guide...
This green LED lights up when the proof of flow contact is BI1 - closed. The VCCX2 Controller is equipped with LEDs that can be used to verify operation and perform troubleshooting. There are LEDs This green LED lights up when the dirty filter switch is closed.
BINARY INPUT LEDs APPLICATION HB LED OPERATING SYSTEM HB LED STATUS 1 & 2 LEDs E-BUS LED POWER LED BACNET LED Figure 19: VCCX2 Controller LED Locations RELAY OUTPUT TERMINALS YS102482 REV1 4992 1002 10uF www.aaon.com STATIC PRESSURE 1002 EXHAUST DUCT...
GND terminal and the “+” (plus) lead on the right side of the Place the “-” (minus) lead on terminal labeled GND and the “+” resistor labeled R85. Be sure to replace the jumper after checking. lead on terminal AI5 on the VCCX2 Controller. DUCT STATIC PRESSURE SENSOR BUILDING PRESSURE SENSOR...
Networked System For a networked single loop system, a range of one to 59 VCCX2 Controllers sharing information, connect the controllers together using AAON communications wire or 18-gauge, two-conductor, twisted pair with shield wire (Belden #82760 or equivalent).
The <MENU> key cancels editing when in Edit Mode. The screen you were editing will return to its original value and the underscore will disappear. A second press of the <MENU> key will return you to the Main Menu. Table 24: Editing Key Functions VCCX2 Controller Technical Guide...
0.0 % XX.X vdc MSTPBaud SA Temp See the following pages for detailed descriptions of NOTE: XXXXX XX.X° the options for each menu. EBUS RA Temp XX Speed XX.X° OA Temp XX.X° 0.0 % CO2Level X ppm VCCX2 Controller Technical Guide...
Used to override relay and analog outputs. Override Air Balance screens that can be used by air Balance balance to set min and max fan speeds. Factory This screen is for AAON factory use only. Testing Table 25: Main Screens VCCX2 Controller Technical Guide...
RA Temp Return air temperature. XX.X° OA Temp Outdoor air temperature. XX.X° OA RH Outdoor air humidity. 0.00% - 100%. X.X % CO2Level Carbon dioxide level. 0.00 ppm to 5000 ppm. X ppm Table 28: Status Screens VCCX2 Controller Technical Guide...
RELAY Relay run time exceeded alarm RUNTIME ECONO Title 24 Economizer alarms FAILURE RET FAN Return/Exhaust fan proving alarm FAILURE DIR FIRE Direct fire heat alarm ALARM Fan Array Controller alarm ALARM Table 29: Alarms Screens VCCX2 Controller Technical Guide...
Maximum fan voltage. 0.0 to 10.0 VDC. Press the 10.0 VDC <UP> and <DOWN> buttons to change the value. RELAY #1 VCCX2 controller relays 1-8. Press the <UP> Default is 10.0. AUTO button to change the value. Default is AUTO.
1. All wiring to be in accordance with local and national electrical codes and specifications. 2. All communication wiring to be 18-gauge minimum, two-conductor, twisted pair with shield. Use Belden #82760 or equivalent. Figure 25: VCCX2 BACnet Connection to MS/TP Network VCCX2 Controller Technical Guide...
Return Air Bypass Modulating Cooling Position AI: 34 Current percentage of the Modulating Chilled Water Signal Modulating Heat Position AI: 35 Current percentage of the Modulating Heating signal (Hot Water or SCR heat) Objects labeled AI are read-only. VCCX2 Controller Technical Guide...
Page 73
B1 Compressor Signal AI: 69 Current Compressor B1 Modulating Cooling Signal B2 Compressor Signal AI: 70 Current Compressor B2 Modulating Cooling Signal B1 Condenser Signal AI: 71 Current B1 Condenser Signal Objects labeled AI are read-only. VCCX2 Controller Technical Guide...
Page 74
Current Compressor C1 Suction Line Temperature (Heat (Heat Pump) Pump) C2 Condenser Suction Temp AI: 107 Current Compressor C2 Suction Line Temperature (Heat (Heat Pump) Pump) C1 Superheat Temperature AI: 108 Current Compressor C1 Superheat Temperature Objects labeled AI are read-only. VCCX2 Controller Technical Guide...
Page 75
D1 Discharge Temperature AI: 141 Current Compressor D1 Discharge Temperature D2 Discharge Temperature AI: 142 Current Compressor D2 Discharge Temperature D1 Leaving Water Temp AI: 143 Current D1 Leaving Water Temperature for WSHP Objects labeled AI are read-only. VCCX2 Controller Technical Guide...
Page 76
See RSMZ Faults Bits on page 91. RSMZ 2 Lockouts AI: 182 Current RSMZ 2 Lockouts See RSMZ Lockouts Bits on page 91. RSMZ 3 Condenser Fan AI: 183 Current RSMZ 3 condenser fan signal Objects labeled AI are read-only. VCCX2 Controller Technical Guide...
Page 77
Current RSMZ 5 Warnings See RSMZ Warnings Bits on page 91. RSMZ 5 Comp VFD Alarms 1 AI: 225 Current RSMZ 5 Comp VFD Alarms 1 See RSMZ Alarms 1 Bits on page 92. Objects labeled AI are read-only. VCCX2 Controller Technical Guide...
Page 78
Current Subcooling Module 2 Sub Cool 1 reading SUB 2 Sub Cool 2 AI: 266 Current Subcooling Module 2 Sub Cool 2 reading SUB 2 Sub Cool 3 AI: 267 Current Subcooling Module 2 Sub Cool 3 reading Objects labeled AI are read-only. VCCX2 Controller Technical Guide...
Page 79
Space Dew Point AI: 285 Current value of the calculated Space Dew Point. Return Dew Point AI: 286 Current value of the calculated Return Dew Point. Objects labeled AI are read-only. VCCX2 Controller Technical Guide...
Warm-Up Mode activates if the Return Target Temperature) Air is below this temperature by one degree Objects labeled AV are read/write. The only sensor values that can be written to are AV points 72, 73, and 76 through 79. VCCX2 Controller Technical Guide...
Page 81
Temperature at which the Low Ambient Relay activates in -30°F (-34.4°C) 70°F (21.1°C) Setpoint the Occupied or Unoccupied Mode Objects labeled AV are read/write. The only sensor values that can be written to are AV points 72, 73, and 76 through 79. VCCX2 Controller Technical Guide...
Page 82
Min Damper Position is proportionally reset between the configured Min Damper Position and the Max Position in High CO2. Objects labeled AV are read/write. The only sensor values that can be written to are AV points 72, 73, and 76 through 79. VCCX2 Controller Technical Guide...
Page 83
Dehumidification. During Coil Temp Reset, this is the lowest Space RH value that corresponds to the High Coil Temp Setpoint. If the VCCX2 is configured for indoor dewpoint control, this point displays Dew Point instead of Humidity. Indoor Humidity Setpoint High...
Page 84
This must be an infrequent event, so the default is 15 minutes. Objects labeled AV are read/write. The only sensor values that can be written to are AV points 72, 73, and 76 through 79. VCCX2 Controller Technical Guide...
Page 85
BMS wants them disabled. Supply Air Dew Point Setpoint AV: 99 When the VCCX2 is configured for DX-DOAS control it modulates the compressors to try to maintain the Supply Air Dew Point Setpoint during dehumidification mode. Objects labeled AV are read/write. The only sensor values that can be written to are AV points 72, 73, and 76 through 79.
BI: 36 Occurs when the Controlling Sensor Temperature rises above the Cooling Mode Enable Setpoint plus the Control Mode High Alarm Offset. Applies only to Space or Return Air Temperature controlled units. Objects labeled BI are read-only. VCCX2 Controller Technical Guide...
Page 87
BI: 76 Status of MHGRV Controller A1 Compressor Enable BI: 77 Current Status of Enable Signal to Compressor A1 A2 Compressor Enable BI: 78 Current Status of Enable Signal to Compressor A2 Objects labeled BI are read-only. VCCX2 Controller Technical Guide...
Page 88
Emergency Shutdown Input on Module D Refrigerant Module 4 Relay 1 BI: 120 Current Status of Compressor 1 Enable Relay Refrigerant Module 4 Relay 2 BI: 121 Current Status of Compressor 2 Enable Relay Objects labeled BI are read-only. VCCX2 Controller Technical Guide...
Page 89
Heat Enable signal is removed and direct fire heating is locked out. Direct Fire Setpoint Override BI: 149 Indicates the max calculated heat rise is limiting the Supply Air Setpoint to a lower value. Objects labeled BI are read-only. VCCX2 Controller Technical Guide...
Need help?
Do you have a question about the VCCX2 and is the answer not in the manual?
Questions and answers