SYSTEM PARAMETERS
9.1 Quick setup parameters
Code
Parameter
Nominal voltage
P1.1
of the motor
Nominal fre-
P1.2
quency of the
motor
Nominal speed
P1.3
of the motor
Nominal current
P1.4
of the motor
Motor
con-
P1.5
nection
P1.6
Min frequency
Autochange
P1.7
Mode
Number of Auxil-
P1.8
iary Pumps
Desired work
P1.9
pressure
Table 9.1: Quick setup parameters
9.2 Advanced PFC settings
Code
Parameter
Work pressure 2 P1.9
P2.1
P2.2
Acceleration
P2.3
Deceleration
P2.4
PI Gain
Table 9.2: Advanced PFC settings
24-hour support (0)201 212 575 • Email: vacon@vacon.com
Min
Max
Unit Default
180
500
V
30
320
Hz
300
20000 rpm
0,2 x
1,5 x
A
I
I
Nunit
Nunit
0,30
1,00
0
P3.1
HZ
0
4
0
3
0
P2.20
kg
Min
Max
Unit
P2.20
kg
0,1
3000,0 S
0,1
3000,0 S
0,0
1000,0 %
ID
230
Check specification
110
400
plate on the motor
Check specification
50,00
111
plate on the motor
Default applies for a 4-
2800
112
pole motor.
Check specification
I
113
Nunit
plate on the motor
Check specification
0,85
120
plate on the motor
Minimum frequency of
30,00
101
pumps
0 = No Autochange
1 = Aux. autochange
without interlocks
2 = Autochange all
4
1603
without interlocks
3 = Aux. autochange
with interlocks
4 = Autochange all with
interlocks
Auxiliary pumps in the
1
1600
system
Desired work pressure
4,0
167
in Kg
Default
ID
Second pressure ref-
5,0
1617
erence.
Activated using DI2
Acceleration time from
3,0
103
0 Hz to maximum fre-
quency
Deceleration time
3,0
104
from maximum fre-
quency to 0 Hz
125,0
118
51
VACON
Note
Note
9