Clock Operation - Vector TCI-W11-H Overview

Universal controller
Hide thumbs Also See for TCI-W11-H:
Table of Contents

Advertisement

Clock operation

TCI-W22 contains a quartz clock with battery back-up (not available in TCI-W11). Up to 8 mode changes based on time
and day of the week may be programmed. Also position an output or select a set point directly with a time schedule. A
blinking clock indicates that the time has not been set or that the unit has been without power for longer than 48 hours.
The time needs to be set to allow time schedules to operate.
Clock setup
Press OPTION > 2 sec. SEL and current time displayed
Press OPTION< 2 sec. to change time,
Minutes blink: UP/DOWN to change, OPTION to save minutes,
Hours blink: UP/DOWN to change, OPTION to save hour,
Press OPTION to save time,
DAY1 blinks: UP/DOWN to change, OPTION to save day
Enable/disable time schedules
Press OPTION > 2 sec. SEL and current time displayed
Press UP:
SEL and PRO displayed, clock symbol blinks
Press OPTION:
Time schedule status displayed OFF or ON:
Press OPTION
OFF/ ON blinks, UP/DOWN to change, OPTION to save
Creating time schedules
Step 1: Select a switching time (Up to 8, Pr01–Pr08)
Press UP while PRO-ON displayed:
Large digits display Pr01, small digits display 00:00
Press OPTION:00:00 blinks
Press UP/DOWN to select Pr01switching time from 00:00–23:45
Press OPTION to save switching time (bar appears indicating step 1 complete):
DAY 1 blinks
Step 2: Apply selected switching time (Pr01) to DAY1 (Mon) – DAY 7 (Sun)
While Pr01 is displayed and DAY1 is blinking:
Press UP: Activate Pr01 switching time for DAY1 (triangle appears on 1),
Press DOWN:
Deactivate Pr01 switching time for DAY1(triangle disappears)
Press OPTION to save Pr01 DAY1 (2
Repeat for DAY2 – DAY7
Step 3: Select action for switching time (Pr01+Days)
After Pro1, DAY1–DAY7 is completed (Pro1 switching time activate or deactivate on desired days), press
OPTION again to come to desired action for Pro1. The following options appear in order:
No = switching time not active
OP = operation mode (select ON (Comfort/Occupied), ECO (Economy/Unoccupied), OFF)
L1 = set point of loop 1 (select set point)
L2 = set point of loop 2 (select set point)
d1 = ON/OFF status of do1 (output must be in manual mode)
d2 = ON/OFF status of do2 (output must be in manual mode)
A1 = set point (0-100%) of ao1 (output must be in manual mode)
After repeatedly pressing OPTION through DAY7:
First available action No appears, blinking:
Press UP/DOWN to scroll through the 8 possible actions (3
Step 4: Complete switching event (e.g. Pro1 = 08:00, DAY 1, Comfort mode)
Available actions blink as you scroll through them, Press OPTION to select one:
Characteristics of action (e.g. 0–100% for A1) appear (4
Press UP/DOWN to select, OPTION to complete
Doc: 70-00-0158, V1.4-20220321
Subject to alteration
nd
bar indicates step 2 complete):
nd
bar indicates step 3 complete)
© Vector Controls GmbH, Switzerland
SEL
SEL
th
bar indicates step 4 complete)
TCI-W Universal Controller
O
PERATION
00:00
DAY1 (Mon)
Pro
PRO
OFF/ON
Pr01
08:00
Pr01
DAY1
1 2 3 4 5 6 7
Pr01
no
Pr01
08:00
Page 6

Advertisement

Table of Contents
loading