Table 13 - Bard W24HY-A Installation Instructions Manual

Wall mounted package heat pump
Table of Contents

Advertisement

Rated
Volts
Model
&
Phase
W18HY-A00, A0Z
A04
230/208-1
A08
W24HY-A00, A0Z
A04
230/208-1
A08
W24HY-B00, B0Z
230/208-3
B05
W24HY-C00, C0Z
460-3
C05
W30HY-A00, A0Z
A05
230/208-1
A10
W30HY-B00, B0Z
B05
230/208-3
B09
W30HY-C00, C0Z
C05
460-3
C09
W36HY-A00, A0Z
A05
230/208-1
A10
 A15
W36HY-B00, B0Z
B05
230/208-3
B09
W36HY-C00, C0Z
C05
460-3
C09
j These "Minimum Circuit Ampacity" values are to be used for sizing the field power conductors. Refer to the National Electrical code (latest
version), Article 310 for power conductor sizing. CAUTION: When more than one field power circuit is run through one conduit, the
conductors must be derated. Pay special attention to note 8 of Table 310 regarding Ampacity Adjustment Factors when more than
three (3) current carrying conductors are in a raceway.
k Maximum size of the time delay fuse or circuit breaker for protection of field wiring conductors.
 Maximum KW that can operate with the heat pump on is 10KW. Full heat available during emergency heat mode.
NOTE: The Maximum Overcurrent Protection (MOCP) value listed is the maximum value as per UL 60335 calculations for MOCP (branch-
circuit conductor sizes in this chart are based on this MOCP). The actual factory-installed overcurrent protective device (circuit
breaker) in this model may be lower than the maximum UL 60335 allowable MOCP value, but still above the UL 60335 minimum
calculated value or Minimum Circuit Ampacity (MCA) listed.
IMPORTANT: While this electrical data is presented as a guide, it is important to electrically connect properly sized fuses and conductor
wires in accordance with the National Electrical Code and all local codes.

TABLE 13

Electrical Specifications
Single Circuit
No. Field
Power
j
Minimum
Circuits
Circuit Ampacity
1
16
1
37
1
58
1
22
1
43
1 or 2
63
1
15
1
30
1
8
1
15
1
24
1
50
1 or 2
76
1
17
1
32
1
44
1
9
1
16
1
22
1
27
1
53
1 or 2
79
1 or 2
84
1
20
1
35
1
47
1
11
1
18
1
24
j
Minimum
k
Maximum
Circuit
External Fuse
Ampacity
or Circuit
Breaker
Ckt.
A
20
40
60
25
45
70
22
20
30
15
15
30
50
80
24
20
35
45
15
20
25
35
60
80
27
90
32
25
35
50
15
20
25
Dual Circuit
k
Maximum
External Fuse
or Circuit
Breaker
Ckt.
Ckt.
Ckt.
B
A
B
42
25
45
52
30
60
52
35
60
52
35
60
Manual
2100-790
Page
39 of 49