SINGLE STAGE HEAT PUMPS LOW VOLTAGE CONTROL CIRCUIT WIRING MODELS W**H W**H*D S**H S**H*D T**H T**H*D Bard Manufacturing Company, Inc. Manual : 2100-516H Bryan, Ohio 43506 Supersedes: 2100-516G File: Volume III Tab 16 Since 1914...Moving ahead just as planned. Date:...
Programmable Programmable Programmable Programmable Model Series S**H T**H 3 & 4 Heat Pump W**H S**H*D Heat Pump with T**H*D 9 & 10 Dehumidification W**H*D “L” terminal is compressor lockout output. This WIRING – LOW VOLTAGE WIRING terminal is activated on a high or low pressure trip by the 230/208V, 1 phase and 3 phase equipment dual primary electronic heat pump control.
TABLE 4 HUMIDITY CONTROLS Part Number Predominate Features 8403-038 SPDT switching, pilot duty 50VA @ 24V (H600A1014) Humidity range 20-80% RH 8403-047 Electronic dehumidistat SPST closes-on-rise (H200-10-21-10) Humidity range 10-90% with adjustable stops TABLE 5 CO2 CONTROLLER Part Number Predominate Features Normally Open SPST relay closes-on-rise 24V dual wave length sensor.
Page 5
BASIC HEAT PUMP WITH OPTIONAL ELECTRIC HEAT NO ECONOMIZER or VENTILATION PACKAGES Low Voltage Wiring Diagram Thermostat 1 Stage Cool #TH5220D1151 2 Stage Heat Bard part #8403-058 "L" is constant 24V output when thermostat is in Em Heat mode Electronic Thermostat Y1 O/B W1/E...
Page 6
Heat Pump with Optional MFAD, CRV, and ERV Ventilation Packaging with Programmable Thermostat (Recommended) Low Voltage Wiring Diagram Electronic Thermostat W1/E Y O/D Bard part #8403-060 Programmable Optional CO Controller Bard part #8403-067 24V Low Voltage Unit Terminal Block Orange...
Page 7
PACKAGING WITH NON-PROGRAMMABLE THERMOSTAT (NO OCCUPIED SIGNAL) Low Voltage Wiring Diagram 1 Stage Cool Thermostat #TH5220D1151 2 Stage Heat Bard part #8403-058 "L" is constant 24V output when thermostat is in Em Heat mode 24V Low Voltage Unit Terminal Block...
Page 8
"L" is constant 24V output when thermostat is in Em Heat mode Low Voltage Wiring Diagram 1 Stage Cool Thermostat #TH5220D1151 2 Stage Heat Bard part #8403-058 Optional CO Controller Bard part #8403-067 24V Low Voltage Unit Terminal Block Orange...
“E” VENT OPTION Figure 5 Heat Pump with Optional Economizer Low Voltage Wiring Diagram 2 Stage Cool Thermostat YO/D W1/E Bard part #8403-060 2 Stage Heat 24V Low Voltage Unit Terminal Block Economizer Wiring Harness MIS-2648 C 1 Factory Jumper Installed.
Page 10
Heat Pump with Dehumidification Sequence and No Ventilation Package using Thermostat part #8403-060 Combination Temperature and Humidity Controller. Low Voltage Wiring Diagram Thermostat Electronic W1/E YO/D Bard part #8403-060 Programmable MIS-2636 A 24V Low Voltage Unit Terminal Block Factory Jumper Installed.
Page 11
HEAT PUMP WITH DEHUMIDIFICATION SEQUENCE WITH NON-PROGRAMMABLE THERMOSTAT Low Voltage Wiring Diagram Thermostat 1 Stage Cool #TH5220D1151 2 Stage Heat Bard part #8403-058 "L" is constant 24V output when thermostat is in Em Heat mode 24V Low Voltage Terminal Block Unit Electronic Humidistat Bard part #8403-047 1 Factory Jumper Installed.
Page 12
Optional CO Controller Low Voltage Wiring Diagram 2 Stage Thermostat Cool YO/D W1/E Bard part 2 Stage #8403-060 Heat Optional CO Controller Bard part #8403-067 24V Low Voltage Unit Terminal Block Orange Brown/White Black Ventilation Packages Black MFAD MIS-2637 C 1 Factory Jumper Installed Must be configured to "no economizer"...
Page 13
HEAT PUMP WITH DEHUMIDIFICATION SEQUENCE & OPTIONAL MFAD, CRV & ERV VENTILATION PACKAGING USING A NON-PROGRAMMABLE THERMOSTAT (NO OCCUPIED SIGNAL) Low Voltage Wiring Diagram Thermostat 1 Stage Cool Bard part #8403-058 2 Stage Heat "L" is constant 24V output when thermostat is in Em Heat mode 24V Low Voltage...
"L" is constant 24V output when thermostat is in Em Heat mode Low Voltage Wiring Diagram 1 Stage Cool 2 Stage Heat Thermostat #TH5220D1151 Bard part #8403-058 Optional CO Controller Bard part #8403-067 24V Low Voltage Terminal Block Unit Orange Brown/White Black...
Page 15
DO NOT CONNECT "L" UNTIL AFTER 8403-060 CONTROLLER IS CONFIGURED TO CS2000 = YES YELLOW 8403-038 TEMPERATURE/HUMIDITY YO/D W1/E H600A1014 CONTROLLER BARD P/N 8403-060 HUMIDITY CONTROLLER BLUE 8403-047 THERMOSTAT TH5220D1151 H200-10-21-10 BARD P/N 8403-058 DEHUMIDSTAT IF OPTIONAL VENT PACKAGE IS INSTALLED, THE "G"...
FIGURE 13 1-STAGE HEAT PUMP WITH OPTIONAL ELECTRIC HEAT WITH OR WITHOUT DEHUMIDIFICATION WITH ECONWM STYLE ECONOMIZER “W” OR “T” VENT OPTION Low Voltage Wiring Diagram Thermostat YO/D W1/E part #8403-060 24V Low Voltage Terminal Block Yellow/White Economizer Wiring Harness Must be energized to enable minimum position.
Page 18
FIGURE 14 HEAT PUMP WITH OPTIONAL CRVMWH-3 OR CHCRV-5 VENTILATION PACKAGING WITH PROGRAMMABLE THERMOSTAT (RECOMMENDED) Low Voltage Wiring Diagram Electronic Thermostat W1/E Y O/D Bard part #8403-060 Programmable Optional CO Controller Bard part #8403-067 24V Low Voltage Unit Terminal Block Yellow...
Page 19
HEAT PUMP WITH OPTIONAL CRVMWH-3 OR CHCRV-5 VENTILATION PACKAGING WITH NON-PROGRAMMABLE THERMOSTAT (NO OCCUPIED SIGNAL) Low Voltage Wiring Diagram 1 Stage Cool Thermostat #TH5220D1151 2 Stage Heat Bard part #8403-058 24V Low Voltage Unit Terminal Block Yellow CHCRV-5 Orange Black...