Model Selectech Communication Diagnostics; Figure 12 Motor Connections - Bard W24HY-A Installation Instructions Manual

Wall mounted package heat pump
Table of Contents

Advertisement

TROUBLESHOOTING GE X13-SERIES ECM2.3

Model SelecTech Communication Diagnostics

The SelecTech motor is communicated through 24 VAC
Model X13 Communication Diagnostics
low voltage (thermostat control circuit wiring).
The X13 motor is communicated through 24 VAC low voltage
(Thermostat Control Circuit Wiring).
1.
Start with unit wiring diagram to confirm proper
1.
Start with unit wiring diagram to confirm proper
connections and voltage (see Figure 12).
connections and voltage (see Figure 11).
2. Initiate a demand from the thermostat and
check the voltage between the common and the
appropriate motor terminal (1-5). ("G" input is
typically on terminal #1, but always refer to wiring
diagram.)
A. If the low voltage communication is not
present, check the demand from the
thermostat. Also check the output terminal
and wire(s) from the terminal strip or control
relay(s) to the motor.
24VAC Common
24VAC "R" Signal through
thermostat output.
Speed Tap 1: Vent Speed
Speed Tap 2: Balanced Climate Speed
Speed Tap 3: Default Speed
Speed Tap 4: Medium Speed
Speed Tap 5: High Speed
24VAC Common
24VAC "R" Signal through
thermostat output.
B. If the motor has proper high voltage as
identified above (If the Motor Is Not Running
2. Initiate a demand from the thermostat and check the
#1), proper low voltage to a programmed
voltage between the common and the appropriate motor
terminal and is not operating, the motor has
terminal (1-5). ("G" input is typically on terminal #1, but
failed and will require replacement.
refer to wiring diagram!)
a. If the low voltage communication is not present, check
the demand from the thermostat. Also check the
output terminal and wire(s) from the terminal strip or
control relay(s) to the motor.
b. If the motor has proper high voltage as identified
above (Motor not Running #1), and proper low voltage
to a programmed terminal, and is not operating, the
motor is failed, and will require replacement.